STUDER INNOTEC HP-COMPACT
User manual HP-COMPACT V3.0 E 25
8 Technical Data
Model
HPC2512 HPC4024 HPC5048 HPC7048
Inverter
Nominal battery voltage
12 V 24 V 48 V 48 V
Input voltage range 9.5 – 17 V 19 – 34 V 38 – 68 V 38 – 68 V
Nominal power @ 25°C
2500 W 4000 W 5000 W 7000 W
Maximum load 30 min. @ 25°C 2800 W 4500 W 6000 W 8000 W
Maximum load 5 sec 3 x Pnom
Maximum load up to short circuit
Maximum asymmetric load up to Pnom
Standby adjustment 1 to 25 W
Cos ϕ
0.1 - 1
Maximum efficiency 93 % 94 % 96 % 96 %
Consumption OFF/Standby/ON 1.4/1.8/10 W 1.7/2/16 W 2/2.5/18 W 2/3/25 W
Output voltage 230 Vac (0 / - 10%)
Output frequency crystal controlled
50 Hz ± 0.05 %
Total harmonic distortion < 2%
Dynamic behaviour on load change 0 → 100 %
0.5 ms
Overload and short circuit protection Automatic disconnection with 3 time restart attempt
Overheat protection Acoustic warning before shut-off - with automatic restart
Battery charger (4 STEP) I-U-Uo-Equalize (every 25 cycles)
Charging current adjustable 0 – 110 A 0 – 100 A 0 – 70 A 0 – 90 A
Input current balance adjustment (Power Sharing) 1 – 30 A 1 – 30 A 1 – 30 A 1 – 50 A
Maximum input voltage 265 Vac
Minimum input voltage Adjustable threshold from 150 to 230 Vac
Input frequency 45 – 65 Hz
Power Factor Correction (PFC) EN 61000-3-2
Battery control (thresholds and times adjustable by the user)
Absorption time 0-4h
End charge cycle voltage 14.4 V 28.8 V 57.6 V 57.6 V
Floating voltage 13.6 V 27.2 V 54.4 V 54.4 V
Equalisation voltage 15.6 V 31.2 V 62.4 V 62.4 V
Deep-discharge protection 10.8 V 21.6 V 43.2 V 43.2 V
Temperature compensation (option CT-35) -3mV / °C / cell
General data
Multifunction contact - potential free (3 points) 16 A – 250 Vac
Max. current on transfer relay 30 A / 6.9 kVA 30 A / 6.9 kVA 30 A / 6.9 kVA 50 A / 11.5 kVA
Transfer time < 20 ms
Weight 33 kg 39 kg 41 kg 48 kg
Dimension h x l x L [mm] 242/288/480 242/288/480 242/288/480 242/288/500
IP protection index IP 20
EEC conformity
EN50081 I/II, EN 55014 – EN 55022, EN 61000-3-2
IEC 801 I/II/III/IV, CEI 555, IEC 1000-3-2, LVD 73/23/EEC
Working range -20 to 55°C
Ventilation from 45°C
Acoustic level without / with ventilation < 10 dB / < 35 dB
Recommended battery capacity (C10) > 5 x Pnom/Unom
Warranty 2 years
Options
Remote control (112 x138 x 25mm / 20 m cable) RCC-01
Remote power sharing (20 m. cable) RPS-01
Battery temp. sensor (58 x 51.5x 22mm / 3 m cable) CT-35
Data may change without any notice