Xantrex Technology 15A12V Battery Charger User Manual


 
Onboard Control and Status Display Panel
975-0401-01-01 1–11
Table 1-1 on page 1–11 summarizes the various fault
conditions that might occur during the operation of the
charger. For suggestions in what to do after a fault condition
is detected, see Table 3-1, “Interpreting Fault and Warning
Indicators” on page 3–4 in Chapter 3, “Troubleshooting”.
Table 1-1
Fault and Warning Indicators
Fault or Warning
Condition
Temp Fan AC Battery Fuse Charger Remote Fault
High Battery Temp
warning; >50°C
See Figure 1-5.
High Battery Temp
fault; >70°C
See Figure 1-5.
Low Battery Temp
warning; <0°C
See Figure 1-5.
Low Battery Temp
fault; < -25°C
See Figure 1-5.
AC input out of range
Warning; 90–108 V
or 255–265 V
See “Input Voltage
Operating and
Derating”.
AC input out of range
fault; <85V or >265V
AC frequency out of
range fault; <45 Hz or
>65 Hz