Xantrex Technology 40A12V Battery Charger User Manual


 
Indicator LEDs on the Onboard Display Panel and Optional Remote Panel
975-0401-01-01 3–5
High Battery Temp
fault (>70°C)
Check the batteries. Do not charge a battery that is
rated other than 12 V nominal for all 12 Vdc chargers
or 24 V nominal for all 24 Vdc chargers. Check that
the battery type and temperature settings match the
actual battery and its conditions.
Disconnect or turn off other charging sources such as
an alternator or the charger on a generator with an
electric start.
Allow the battery (or batteries) to cool to normal
operating temperature. See Appendix A,
“Specifications”.
Low Battery Temp
warning (<0°C)
Check the batteries. Do not charge a frozen battery.
Charging a frozen battery may present a risk of
explosion. Check that the battery type and
temperature settings match the actual battery.
Allow the battery (or batteries) to warm up to a
temperature that is above freezing before charging. If
the temperature decreases further and a BTS is
connected to the coldest battery, the charger will
indicate a fault and shut down. Do not attempt to
charge without warming. See Appendix A,
“Specifications”.
Flashing LED Solid LED
Table 3-1
Interpreting Fault and Warning Indicators
Fault or Warning
Condition
Temp Fan AC Battery Fuse Charger Remote Fault
Solution