Basic 32 Loader Control UGC007/0702
D-6 Fault Messages and Error Codes
003D INVALID SEQUENCER
LENGTH/POSITION
A sequencer instruction (SQO, SQC,
SQL) length/position parameter is
greater than 255.
Recoverable Correct the user program, then re-compile,
reload the program and enter the Run mode.
003E INVALID BIT SHIFT OR
LIFO/FIFO
PARAMETER
A BSR or BSL instruction length
parameter is greater than 2048 or an
FFU, FFL, LFU, LFL instruction length
parameter is greater than 128 (word
file) or greater than 64 (double word
file)
Recoverable Correct the user program or allocate more
data file space using the memory map, then
reload and Run.
003F COP/FLL OUTSIDE OF
DATA FILE SPACE
A COP or FLL instruction length
parameter references outside of the
entire data space.
Recoverable
Correct the program to ensure that the
length and parameter do not point outside
of the data file space.
Re-compile, reload the program and enter
the Run mode.
0050 CONTROLLER TYPE
MISMATCH
A particular controller type was
selected in the user program
configuration, but did not match the
actual controller type.
Non-User
Connect to the hardware that is specified
in the user program, or
Reconfigure the program to match the
attached hardware.
0051 BASE TYPE
MISMATCH
A particular hardware type (AWA,
BWA, BXB) was selected in the user
program configuration, but did no
match the actual base.
Non-User
Connect to the hardware that is specified
in the user program, or
Reconfigure the program to match the
attached hardware.
0052 MINIMUM SERIES
ERROR
The hardware minimum series
selected in the user program
configuration was greater than the
series on the actual hardware.
Non-User
Connect to the hardware that is specified
in the user program, or
Reconfigure the program to match the
attached hardware.
0070 EXPANSION I/O
TERMINATOR
REMOVED
(MicroLogix 1500 only)
The required expansion I/O
terminator was removed.
Non-Recoverable
Check the expansion I/O terminator on the
last
I/O module.
Cycle power.
xx71
(1)
EXPANSION I/O
HARDWARE ERROR
The controller cannot communicate
with an expansion I/O module.
Non-Recoverable
Check connections.
Check for a noise problem and be sure
proper grounding practices are used.
Replace the module.
Cycle power.
xx79
(1)
EXPANSION I/O
MODULE ERROR
An expansion I/O module generated
an error.
Non-Recoverable
Refer to the I/O Module Status (IOS) file.
Consult the documentation for your
specific I/O module to determine possible
causes of a module error.
0080 EXPANSION I/O
TERMINATOR
REMOVED
(MicroLogix 1500 only)
The required expansion I/O
terminator was removed.
Non-User
Check expansion I/O terminator on last I/O
module.
Cycle power.
xx81
(1)
EXPANSION I/O
HARDWARE ERROR
The controller cannot communicate
with an expansion I/O module.
Non-User
Check connections.
Check for a noise problem and be sure
proper grounding practices are used.
Replace the module.
Cycle power.
Error
Code
(Hex)
Advisory Message Description Fault
Classification
Recommended Action