Press MODE button to get into program mode.
Go to screen number 25 and select the number of slaves you wish to use, 01 thru 04.
SL AVES CONNECTED 25
#XX
Go to screen number 24 and select the number of sensors, relays and auxiliaries.
42RETSAM
SN S : X RE L AY : X AUX : X
02PU-TESKROWTEN
MASTER PBXXXXXXXXXX
Screen number
Screen number
Screen number
Go to screen number 20 and set up your Network master and slave operations.
(Setup slave operations prior to Network Set-up on Master Controller.)
PI D INTERVAL XX 34
KP XX K I XX KD XX
Screen number
PID
Proportional - Integral - Derivative Control
I
nterval - time in seconds that the PID updates
KP - Proportional control (01 - 30) - Band in degrees above and below setpoint
K
I - Integral control (01 - 99) - Adjustable in % 0.0 - 1.0
KD - Derivative control (01 - 99) - Adjustable in % 0.0 - 10.0
PID Interval:
Default Values: Interval=05; KP=06; KI=05; KD=01
NOTE: DO NOT change the default values unless
directed to do so in consultation with factory
technical support. Changing of these parameters
may create adverse operating conditions.
NOTE: Refer to screen number 34 (PID)
Master Unit with Slaves
Refer to page 36 for the Master/Slave diagram.