GP Series Portable Chillers Chapter 6: Troubleshooting 53 of 90
Chiller too small for load
Verify with sales representative
the sizing of the chiller for the
Low Condenser Differential
Pressure Warning
18 W
Low discharge pressure or
high suction pressure
Condenser Inlet Temp Sensor
Failure (optional with sensor
pack)
19 W
Sensor wires loose from
controller terminal block
Verify wiring at terminal block.
.
Sensor wires broke between
sensor and controller terminal
Replace temperature sensor
Chiller In Fluid Temp Sensor
Failure
20 W
Sensor wires loose from
controller terminal block
Verify wiring at terminal block.
.
Sensor wires broke between
sensor and controller terminal
Replace temperature sensor
Evaporator Differential Pressure 21 W
Blocked Y-strainer
opening blow-down valve or
High Discharge Pressure Warning 22 W
Dirty air cooled condenser or
inlet filter
Clean filter or condenser
Dirty water cooled condenser
or condenser valve failure
Clean condenser or verify
operation of condenser valve
Ambient air or condenser
water temperature too high
Verify supply temperature or air
removal capacity.
Too much refrigerant in
system.
Contact Customer Service for
assistance
Liquid line valves closed.
Verify operation of valve and
wiring on controller
High Fluid Temp Warning 23 W
Fluid temperature higher than
parameter.
Verify parameter and adjust if
necessary.
Refrigeration system fault
Check for any refrigeration
system fault
Chiller too small for load
Verify with sales representative
the sizing of the chiller for the
CC = Compressor Critical SC = System Critical PC = Process Critical W = Warning
High Level Fault 24 W
Fluid level higher than
parameter setting.
Verify value in parameter
Too much fluid in system
Open drain valve and remove
some fluid from system so that
level is below high level fault.
High Level Warning 25 W
Fluid level higher than
parameter setting.
Verify value in parameter
Too much fluid in system
Open drain valve and remove
some fluid from system so that
level is below high level
Compressor Differential Pressure
Fault
26 CC
Low discharge pressure or
high suction pressure
High Suction Pressure Warning 27 W
From Process fluid
temperature too high
Verify flow through system.
Make corrections as necessary.
Low Discharge Pressure Warning
Verify ambient air temperature