Chicago Electric 95065 Power Screwdriver User Manual


 
SKU 95065 For technical questions, please call 1-800-444-3353 Page 6
Outlets for 2-Prong Plug
Double insulated tools may be used in
either of the 120 volt outlets shown in
the preceding illustration. (See Outlets
for 2-Prong Plug.)
Extension Cords
Grounded tools require a three wire
extension cord. Double Insulated
tools can use either a two or three wire
extension cord.
As the distance from the supply outlet
increases, you must use a heavier
gauge extension cord. Using exten-
sion cords with inadequately sized wire
causes a serious drop in voltage, result-
ing in loss of power and possible tool
damage. (See Table A.)
The smaller the gauge number of the
wire, the greater the capacity of the
cord. For example, a 14 gauge cord
can carry a higher current than a 16
gauge cord. (See Table A.)
When using more than one exten-
sion cord to make up the total length,
make sure each cord contains at least
the minimum wire size required. (See
Table A.)
If you are using one extension cord for
more than one tool, add the nameplate
amperes and use the sum to determine
the required minimum cord size. (See
Table A.)
If you are using an extension cord out-
doors, make sure it is marked with the
sufx “W-A” (“W” in Canada) to indicate
it is acceptable for outdoor use.
2.
1.
2.
3.
4.
5.
6.
Make sure the extension cord is proper-
ly wired and in good electrical condition.
Always replace a damaged extension
cord or have it repaired by a qualied
electrician before using it.
Protect the extension cords from sharp
objects, excessive heat, and damp or
wet areas.
RECOMMENDED MINIMUM WIRE
GAUGE FOR EXTENSION CORDS*
(120/240 VOLT)
NAMEPLATE
AMPERES
(at full load)
EXTENSION CORD
LENGTH
25’
50’
75’
100’
150’
0 – 2.0 18 18 18 18 16
2.1 – 3.4 18 18 18 16 14
3.5 – 5.0 18 18 16 14 12
5.1 – 7.0 18 16 14 12 12
7.1 – 12.0 18 14 12 10 -
12.1 – 16.0 14 12 10 - -
16.1 – 20.0 12 10 - - -
TABLE A
* Based on limiting the line
voltage drop to ve volts at
150% of the rated amperes.
Symbology
Double Insulated
Canadian Standards
Association
Underwriters Laboratories, Inc.
V~
Volts Alternating Current
A
Amperes
n
0
xxxx/min.
No Load Revolutions per
Minute (RPM)
7.
8.