Reference Manual
00809-0100-4952, Rev BA
Section 1: Introduction
February 2014
Introduction
1.2 Receiving and inspection
The 0085 Pipe Clamp Sensor comes in several different types of materials and clamp sizes so it's
important to inspect and verify that the appropriate model was delivered before installation.
Upon receipt of the shipment, check the packing list against the material received and the
purchase order. Report any damage to the carrier.
1.3 Returning the product
To expedite the return process, call the Rosemount National Response Center toll-free at
800-654-7768. This center, available 24 hours a day, will assist you with any needed information
or materials.
The center will ask for the following information:
Product model
Serial numbers
The last process material to which the product was exposed
The center will provide:
A Return Material Authorization (RMA) number
Instructions and procedures that are necessary to return goods that were exposed to
hazardous substances
Note
If a hazardous substance is identified, a Material Safety Data Sheet (MSDS), required by law to be
available to people exposed to specific hazardous substances, must be included with the
returned materials.
1.4 Considerations
Information in this manual applies to circular pipes only. Consult Rosemount Customer Central
for instruction regarding other uses.
1.4.1 Limitations
Functional
The most accurate and repeatable surface temperature measurement occurs with the following
insulation best practices:
Use weather proof insulation with aluminum cladding
Install insulation extending at least 0.5 meters in each direction from sensor (at least 1
meter total)
Insulate the sensor extension
Install insulation with minimal gaps to isolate sensor as much as possible from ambient
conditions.