GE MM300 Dust Collector User Manual


 
COMMUNICATIONS GUIDE RS485 INTERFACE (MODBUS RTU)
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE 25
40869 0364 CBCT Ground Trip Level 5 151 1 A F2* 151 1
40870 0365 Ground Trip Delay On Start 0 100 1 s F2 0 1
40871 0366 Ground Alarm Delay On Run 0 60 1 s F1 10 1
40872 0367 Ground Trip Delay On Run 0 50 1 s F2 0 1
40873 0368 Reserved --- --- --- --- --- --- 1
40874 0369 Reserved --- --- --- --- --- --- 1
LOAD INCREASE
40875 036A Load Increase Alarm Level 50 151 1 %FLA F1* 151 1
40876 036B Reserved --- --- --- --- --- --- 1
40877 036C Reserved --- --- --- --- --- --- 1
40878 036D Reserved --- --- --- --- --- --- 1
PHASE UNDERVOLTAGE (REQUIRED=IO_B)
40879 036E Undervoltage Alarm Level 60 100 1 %MNV F1* 100 1
40880 036F Undervoltage Alarm Delay 1 60 1 s F1 30 1
40881 0370 Undervoltage Trip Level 60 100 1 %MNV F1* 100 1
40882 0371 Undervoltage Trip Delay 1 60 1 s F1 30 1
40883 0372 Reserved --- --- --- --- --- --- 1
▼▼
40887 0376 Reserved --- --- --- --- --- --- 1
AUXILIARY UNDERVOLTAGE PROTECTION (REQUIRED=IO_C)
40888 0377 Aux U/V Alarm 60 91 1 %NCV F1* 91 1
40889 0378 Aux U/V Alarm Delay 1 60 1 s F1 5 1
40890 0379 Aux UV Trip 60 91 1 %NCV F1* 91 1
40891 037A Aux UV Trip Delay 1 60 1 s F1 5 1
40892 037B Reserved --- --- --- --- --- --- 1
40893 037C Reserved --- --- --- --- --- --- 1
40894 037D Reserved --- --- --- --- --- --- 1
PHASE OVERVOLTAGE (REQUIRED=IO_B)
40895 037E Overvoltage Alarm Level 101 121 1 %MNV F1* 121 1
40896 037F Overvoltage Alarm Delay 1 60 1 s F1 30 1
40897 0380 Overvoltage Trip Level 101 121 1 %MNV F1* 121 1
40898 0381 Overvoltage Trip Delay 1 60 1 s F1 30 1
40899 0382 Reserved --- --- --- --- --- --- 1
40900 0383 Reserved --- --- --- --- --- --- 1
40901 0384 Reserved --- --- --- --- --- --- 1
40902 0385 Reserved --- --- --- --- --- --- 1
PHASE REVERSAL (REQUIRED=IO_B)
40903 0386 Voltage Phase Reversal 0 2 1 --- FC140 1 1
40904 0387 Reserved --- --- --- --- --- --- 1
40905 0388 Reserved --- --- --- --- --- --- 1
40906 0389 Reserved --- --- --- --- --- --- 1
40907 038A Reserved --- --- --- --- --- --- 1
VT FUSE FAIL (REQUIRED=IO_B)
40908 038B VT Fuse Fail 0 2 1 --- FC140 0 1
40909 038C Reserved --- --- --- --- --- --- 1
40910 038D Reserved --- --- --- --- --- --- 1
Modbus Hex Description Min Max Step Units Format Default Size in
Words