GE MM300 Dust Collector User Manual


 
46 MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU) COMMUNICATIONS GUIDE
7Vbn Direct
8 Vcn Direct
FC177 16 bits LED Color Invert
0 Green/Red
1Red/Green
FC178 16 bits Motor Status
Bit 0 Lockout
Bit 1 Non-Lockout Trip
Bit 2 UVR Pending
Bit 4 Running
Bit 5 Precontactor
Bit 6 Starting
Bit 8 Inhibit
Bit 9 Stopped
Bit 10 Self Test Fault
Bit 11 Alarm
Bit 12 Forward
Bit 13 Reverse
Bit 14 Low Speed
Bit 15 High Speed
FC179 32 bits Alarm Status 1
Bit 0 Any Alarm
Bit 1 Thermal Level Alarm
Bit 2 Ground Fault Alarm
Bit 3 Acceleration Alarm
Bit 4 Phase Reversal Alarm
Bit 5 UnderPower Alarm
Bit 6 UnderVoltage Alarm
Bit 7 OverVoltage Alarm
Bit 9 UnderCurrent Alarm
Bit 10 Unbalance Alarm
Bit 11 RTD 1 Alarm
Bit 12 RTD 2 Alarm
Bit 13 RTD 3 Alarm
Bit 14 RTD 4 Alarm
Bit 15 RTD 5 Alarm
Bit 16 RTD 6 Alarm
Bit 17 RTD Open/Short Alarm
Bit 18 RTD Open/Short Alarm
Bit 19 Process ILock A Alarm
Bit 20 Process ILock B Alarm
Bit 21 Process ILock C Alarm
Bit 22 Process ILock D Alarm
Bit 23 Process ILock E Alarm
Bit 24 Process ILock F Alarm
Bit 25 Process ILock G Alarm
Bit 26 Process ILock H Alarm
Code Type Definition