Main Line
6" Rigid Pipe (0.037) at 20' ................ 0.740
Branch Line
4" Rigid Pipe (0.075) at 10' ................ 0.750
4" Flex Pipe (0.28) at 5' ........................ 1.400
Elbows/Branches
6" 45˚ Y-Branch ................................ 0.329
4" 45˚ Elbow ........................................ 0.225
Additional Factors
Seasoned Filter ................................ 1.000
Total Static Pressure Loss ................ 4.444
Additional Factors Static Pressure






4. 


Note: Always account for a seasoned filter,
so you don't end up with a system that only
works right when the filter is clean.
Note: When calculating static pressure loss
to determine if multiple lines can be left open
at the same time, only include the main line
numbers once.
3. 

5. 
Figure 48 
Page 31
ExampleData Sheet Performance
Curve Figure 47 

Figure 46
        




-6-
G0440/G0441/G0443 Cyclone Dust Collectors
.(
(
¿-
+,
,*
&
¿)
'+
,
¿-
('
,
¿-
')
&
¿'
&*
(
¿)
)(
(
¿)
¢,
(,
(
¿)
*.
&
¿&+
('
,
¿-
¢,
('
,
¿-
¢,
&,
&
¿)
G0440 MACHINE
DATA SHEET
Customer Service #: (570) 546-9663 • To Order Call: (800) 523-4777 • Fax #: (800) 438-5901
MODEL G0440
2 HP TWO-STAGE CYCLONE DUST COLLECTOR
©2005 BY GRIZZLY INDUSTRIAL
®
Specications, while deemed accurate, are not guaranteed. 2/2005.
The airow test probe is located 1.5x duct diameter upstream from the
air inlet. Test pipe length is a minimum of 10x duct diameter.
2 HP GRIZZLY DUST COLLECTOR PERFORMANCE RESULTS
Max CFM Max SP HP Volts Inlet Impeller
1354 10.4 2 HP 220V 7" 14-1/2"
Restrictor Plate
(inch)
Dia. 7" Dia.
6"
Dia.
5"
Dia. 4" Dia. 3" Dia.2"
Static Pressure
(Inch/H2O)
2.5 3.2 5.1 7.8 9.2 10.0
CFM 1354 1266 1070 829 586 338
Performance Curve
2500
2250
2000
1750
1500
1250
1000
750
500
250
0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0
1354
CFM
STATIC PRESSURE (Inch/H2O)
Figure 47






       
      
       
      
   
    