OM-480 Page 37
10-3. Grounding When Supplying Building Systems
ST-800 576-B
1 Equipment Grounding
Terminal
2 Grounding Cable
Use #10 AWG or larger insulated
copper wire.
3 Ground Device
Y Ground generator to system
earth ground if supplying
power to a premises (home,
shop, farm) wiring system.
GND/PE
1 2
Use ground device as stated
in electrical codes.
2
3
10-4. How Much Power Does Equipment Require?
S-0623
1 Resistive Load
A light bulb is a resistive load and
requires a constant amount of pow-
er.
2 Non-Resistive Load
Equipment with a motor is a non-re-
sistive load and requires approxi-
mately six times more power while
starting the motor than when run-
ning (see Section 10-8).
3 Rating Data
Rating shows volts and amperes,
or watts required to run equipment.
VOLTS 115
4.5
60
AMPS
Hz
1
2
3
3
EXAMPLE 1: If a drill uses 4.5 amperes at 115 volts, calculate its running power
requirement in watts.
4.5 A x 115 V = 520 W
The load applied by the drill is 520 watts.
EXAMPLE 2: If three 200 watt flood lamps are used with the drill from Example 1,
add the individual loads to calculate total load.
The total load applied by the three flood lamps and drill is 1120 watts.
(200 W + 200 W + 200 W) + 520 W = 1120 W
AMPERES x VOLTS = WATTS