2-12. Electrical Service Guide
Input Voltage 200 230 460 575
Input Amperes At Rated Output 50 44 22 17
Max Recommended Standard Fuse Or Circuit Breaker Rating In
Amperes
80 70 35 25
Min Input Conductor Size In AWG/Kcmil 8 8 10 12
Max Recommended Input Conductor Length In Feet (Meters) 93 (28) 124 (38) 329 (100) 313 (95)
Min Grounding Conductor Size In AWG/Kcmil 8 8 10 12
Reference: 1996 National Electrical Code (NEC) S-0092J
2-13. Selecting A Location And Connecting Input Power
Have only qualified persons make
this installation.
1 Rating Label
Supply correct input power.
Y Special installation may be
required where gasoline or
volatile liquids are present
see NEC Article 511 or CEC
Section 20.
801 788-A / Ref. 800 797-C
18 in (457 mm)
for airflow
Size and ratings must comply with ap-
plicable codes. Install conductors in
conduit or equivalent into a deener-
gized line disconnect device (see
Section 2-12).
GND/PE
Connect First
L1
L2
GND/PE
1