Miller Electric XMT 4-Rack Welder User Manual


 
Ref. S-0092-G
OM-815 Page 11
Table 4-2. Electrical Service Requirements*
Input Voltage
230 460
Recommended Standard Fuse Or Circuit Breaker Rating In Amperes
1
250 125
Input Conductor Size In AWG/Kcmil
2
1/0 4
Max Input Conductor Length In Feet (Meters)
3
229 (70) 397 (121)
Grounding Conductor Size In AWG/Kcmil
4
4 6
*
These values are calculated from the 1993 edition of the National Electrical Code (NEC).
1 Recommended fuse or circuit breaker size is that closest to 150% of rated input amperage of the welding power source. Article 630-12(a) of NEC
allows fuse or circuit breaker sizing up to 200% of rated input amperage.
2 Input conductor size is for insulated copper wire with 75°C rating with not more than three single current-carrying conductors in a cable or raceway
(Table 310-16 of NEC).
3 Maximum length is to prevent more than a 3% voltage drop between service entrance and input terminals of the welding power source (Articles
210-19(a) and 215-2(b) of NEC).
4 The grounding conductor shall be colored or identified as specified in the NEC. Grounding conductor size for copper wire is not required to be larger
than input conductor (Article 250-95 of NEC).
SECTION 5 MAINTENANCE & TROUBLESHOOTING
ELECTRIC SHOCK can kill.
Do not touch live electrical parts.
Turn Off welding power sources, and disconnect input power to rack before inspecting, maintaining, or servicing.
Maintenance to be performed only by qualified persons.
WARNING
5-1. Routine Maintenance
Turn Off all power before maintaining.
ST-151 267-B
6 Months
OR
During Heavy Service,
Clean Monthly
Blow Out
Or
Vacuum
Inside
3 Months
Tape Or
Replace
Cracked
Cables
Clean
And
Tighten Weld
Connections
Replace
Unreadable
Labels
See
Section
7
Figure 5-1. Maintenance Schedule