OUTBACK GTFX AND GVFX CERTIFICATE OF COMPLIANCE TO UL1741
UTILITYINTERACTIVE INVERTERS
OutBack GTFX and GVFX inverters comply with UL1741 for utility-interactive inverters. The following
specications refer to exporting power to a simulated utility source of less than 1% voltage total
harmonic distortion (THD).
The output of the GTFX or GVFX exceeds the minimum power factor of 0.85 specied in UL1741
section 45.2.2. Typical power factor is 0.96 or better.
The THD of the RMS (root/means/square) current is less than 5 percent of the fundamental under
the conditions of UL1741 section 45.4.2. Individual odd harmonics do not exceed the limits
specied in Table 45.1 of UL1741. Individual even harmonics do not exceed the limits specied in
Table 45.2 of UL1741.
The GTFX and GVFX inverters cease to export power to the simulated utility source under islanding
conditions specied in section 46.3 of UL1741.
The GTFX and GVFX inverters cease to export power to the simulated utility source after the
output voltage and frequency of the simulated utility source are adjusted to each of the conditions
specied in Table 46.1 of UL1741 within the time specied in that table. All production GTFX and
GVFX inverters are tested to comply with the table below as specied in section 46.2 of UL1741.
Condition Voltage Range (VAC) Frequency (Hz) Seconds Allowed Cycles Allowed
A <60 60 0.1 6
B <=60 to <105.6 60 2 120
C >=105.6 to <=132 60 no cessation no cessation
D >132 to <164.4 60 2 120
E >=164.4 60 0.033 2
F 120 <59.3 0.1 6
G 120 >60.5 0.1 6
3