Studer Innotec XPC 1648 Battery Charger User Manual


 
STUDER INNOTEC
XP-COMPACT
6.1 Standard setting
The XP-COMPACT is delivered with the following default setting:
6.1.1 Battery voltage
Low voltage 11.6V / 23.2V / 46.4V
Float Charge 13.5V / 27.0V / 54.0V
End of Charge Voltage 14.4V / 28.8V / 57.6V
Equalization 15.3V / 30.6V / 61.2V
Absorption Time: 2 Hours
6.1.2 Auxiliary contact
Active in case of defect or manual turn off with the LED 10/11/12/13
6.2 Reset value
When the XP-COMPACT is to be connected to a battery or after an interruption (RESET), it is al-
ways programmed with these standard settings.
In order to get to these settings during operation you must press the three Push Buttons 20/21/22
simultaneously for a minimum of 2 seconds.
6.3 Battery voltages and absorption time
The voltage levels (low voltage, float charge, end of charge and equalization) and the duration of
the absorption charge can be changed.
The display of these voltages and the times in the program mode are in accordance with the dia-
gram shown below:
6.3.1 Table of voltage and timing threshold
Low voltage
LED 13
Float Charge
LED 12
Absorption
LED 11
Equalization
LED 10
Absorpt. time
LED 10->13
LED 12V 24V 48V 12V 24V 48V 12V 24V 48V 12V 24V 48V
14 12.0 24.0 48.0 13.7 27.4 54.8 15.0 30.0 60.0 15.5 31.0 62.0 4 h
15 11.8 23.6 47.2 13.6 27.2 54.4 14.8 29.6 59.2 15.4 30.8 61.6 3 h
16
11.6 23.2 46.4 13.5 27.0 54.0
14.6 29.2 58.4
15.3 30.6 61.2 2 h
17 11.4 22.8 45.6 13.4 26.8 53.6
14.4 28.8 57.6
15.2 30.4 60.8 1 h
18 11.2 22.4 44.8 13.3 26.6 53.2 14.2 28.4 56.8 15.1 30.2 60.4 0 1Min.
The heavy printed values show the standard settings.
6.3.2 Set the voltage and timing threshold
The programming is done in accordance with the following steps:
Push and hold down, the Push Button 21 (Program) and the Push Button 19 (Change status) for
minimum 2 seconds simultaneously.
OFF
Over Temp.
Overload
ON/OFF
(Select)
(Change status)
Battery
Low/High
RESET
ALARM
15
16
17
18
1921
13
12
11
10
20
14
With the Push Button 20 (select) select with of the
battery level and the absorption time to be changed.
These four red LED show the function set:
Low voltage LED 13
Float charge LED 12
Absorption (End of charge) LED11
Equalization LED 10
Absorptions Time LED 10/11/12/13
With the Push Button 19 (Change status) set the
desired parameter (voltage or the time) to modify
(LED 14/15/16/17/18). Push Button 19 (Change
status) to set the desired value according to the
User manual XP-COMPACT V2.0 E
18