Thomas & Betts 20 Battery Charger User Manual


 
Part No. 90-0123-00
Libertycombi.p65 10/26/98
19
1. Do not equalize gel cell batteries.
Check remote default settings.
2. Always monitor the equalize charge
cycle. Provide proper ventilation for
battery fumes. Do not allow any sparks
during equalizing. If one or more cells
begin to overflow, terminate the equalize
cycle.
3. Check the battery electrolyte both
before and after the equalizing charge.
Do not expose the battery plates to air.
Leave the battery caps on while
equalizing. Top off after equalizing.
4. Remove all loads from the DC
system before equalizing. Some DC
loads may not tolerate the high charge
voltage.
5. With the Remote Control Panel
the
battery state-of-charge LEDs sequence
during equalizing. When the equalization
cycle is complete, the charge automati-
cally goes to float and the green float LED
battery status light is on.
With Link
Instrumentation, the red charge LED
flashes during the equalizing cycle. When
the equalization cycle is complete, the
charger automatically goes to float and the
green float LED is illuminated.
WARNINGS
BATTERY CHARGING