4
Internal Battery Insertion
8
9
10
Rack Installation
(continued)
Insert Internal Batteries
(Slide Into Battery Pack Cabinet)
Connect 4 Sets of Red/Black Internal Battery
Connectors (Connect Black to Black and
Red to Red.)
Restore Battery Cover Plate and Battery
Pack Front Panel (Screw Into Place)
8 9
10
Connection
The rear panel of the 4U battery pack includes
two polarized Anderson connectors with
removable retention brackets attached over the
connector openings. The included detachable
battery pack cable includes two polarized
Anderson connectors . One of the battery pack
cable connectors fits into one of the connectors on
the battery pack rear panel and the other
connector fits into the external battery pack
connector at the rear panel of the UPS system
power module (or at the rear panel of an
additional daisy-chained battery pack).
D
C
B
A
UPS Power Module Connection
Remove the retention brackets from the
UPS system power module's external battery
pack connector and one of the battery pack's
rear panel connectors .
Insert one end of the detachable power
cable into each connector. (See the UPS
manual for the external battery connector
description and location.)
Attach the retention brackets to the right of
each connector, using the preexisting holes set
to the right of the original bracket position.
DC
A
B
1
2
3
Additional Battery Pack Connection (Daisy-Chaining)
Connect multiple battery packs to a single UPS system by connecting the first battery pack to the UPS system power module's external battery connector, then
daisy-chaining the others by linking a connector on the second battery pack to a connector on the first, a connector on the third to a connector on the second and so
on. Secure each connector with the included connector retention bracket, following the procedure outlined in the UPS Power Module Connection section.
Note: When daisy-chaining multiple battery packs, they should be identical models of similar age and level of wear. Multiple battery packs provide longer runtimes, but also require
longer recharge times.
Warning: Always use the connector retention brackets to secure the battery pack connections. Do not attempt to operate the UPS system without the connector retention brackets.