Xantrex Technology HF 1800 Battery Charger User Manual


 
Warning Messages
975-0390-01-01 5–5
Warning Messages
Warning messages in the form of audible alarms and error codes that
appear on the display panel screen to alert you to an impending system
change. Warnings do not affect operation.
With the exception of the error codes displayed on the screen, only the
audible alarm can be turned ON or OFF. Follow the steps in Chapter 3,
“To adjust the alarm setting:” on page 3–4 to change the alarm settings.
The error codes are listed in Table 5-1 below. The text in the Error Code
column appears on the display screen of the display panel.
Table 5-1
Error Codes Displayed on the Display Panel Screen
Error Code Condition Mode Action
E01
Low battery voltage
shutdown
(< 10.5 Vdc)
Inverting Check battery status and recharge if
necessary.
Check for proper DC cable sizing.
Check for loose connections and tighten if
necessary.
E02
High battery voltage
shutdown
(> 15.5 Vdc)
Inverting Check for external charging sources, such
as an over voltage alternator, and
disconnect if necessary.
E03
AC output overload
shutdown
Inverting Reduce the loads connected to the AC
outlet of the unit.
Check appliances that have high-surge
ratings and disconnect if necessary.
E04
Over-temperature
shutdown
Inverting Reduce the loads connected to the AC
outlet of the unit.
Check that the ventilation grille is not
blocked.
Check for ambient temperature and move
the unit to a cooler location whenever
possible.
E05
Low battery voltage
detected
(< 11.0 Vdc)
Inverting Check battery status and recharge if
necessary.
Check for proper DC cable sizing.
Check for loose connections and tighten if
necessary.
E06
AC output overload
warning
Inverting Reduce the loads connected to the AC
outlet of the unit.