Command Set
4-
18
ADAM 4000 Series User’s Manual
ADAM-4018+ Command Table
Command Syntax Command Name Command Description Page No.
%AANNTTCCFF Configuration Set the address, input range, baud
rate, data format, checksum status
and/or integration time for the
specified analo
input module
5-4
$AA2 Configuration Status Return the configuration
parameters for the specified analog
input module
5-10
$AAF Read Version Return the firmware version code
from the specified analog input
module
5-12
$AAM Read Module Name Return the module name from the
specified analo
input module
5-13
#AA Read Analog Input
from all Channels
Return the input value from all
channels of the specified analog
module
5-14
#AAN Read Analog Input
from Channel N
Return the input value from
channels number N of the
specified analo
input module
5-16
$AA5VV Enable/disable
Channels for
Multiplexing
Enables/disables multiplexing
simultaneously for seperate
channels of the specified input
module
5-17
$AA6 Read Channel
Status
Ask the specified input module to
return the status of all eight
channels
5-18
$AAB Get Operating Status
Get the channel operating status When
bit value is 0, it mean this channel is in
normal operating, when bit value is 1, it
mean this channel is opening wire
5-24
$AA3 CJC Status Returns the value of the CJC
sensor for a specified analog input
module
5-25
$AA9SNNNN
CJC Offset
Calibration
Calibrates an analog input module to
adjust for offset errors of its CJC
sensors
5-26
$AA0Ci Span Calibration
Gain error calibrate of assignment
channel, User have to input the external
standard source for calibrating process
5-27
(Continued on following page)