Agilent Technologies 5749A Welding System User Manual


 
Appendix A Specifications
90 Series N5700 User’s Guide
Agilent Models N5741A – N5752A and N5761A – N5772A
Model
N5741A
N5761A
N5742A
N5762A
N5743A
N5763A
N5744A
N5764A
N5745A
N5765A
N5746A
N5766A
N5747A
N5767A
N5748A
N5768A
N5749A
N5769A
N5750A
N5770A
N5751A
N5771A
N5752A
N5772A
Series and Parallel Capability:
Parallel operation Up to 4 identical units can be connected in master/slave mode with single–wire current balancing
Series operation Up to 2 identical units can be connected using external protection diodes
Savable states:
In volatile memory 16 (in memory locations 0-15)
Interface Capabilities:
GPIB
LXI Compliance
USB 2.0
10/100 LAN
SCPI - 1993, IEEE 488.2 compliant interface
Class C (only apples to units with the LXI label on the front panel)
Requires Agilent IO Library version L.01.01 and up, or 14.0 and up
Requires Agilent IO Library version L.01.01 and up, or 14.0 and up
Environmental Conditions:
Environment
Operating temp.
Storage temp.
Operating humidity
Storage humidity
Altitude
LED statement
Indoor use, installation category II (AC input), pollution degree 2
0°C to 40°C @ 100% load
–20°C to 70°C
30% to 90% relative humidity (no condensation)
10% to 95% relative humidity (no condensation)
Up to 3000 meters.
Above 2000m, derate the output current by 2%/100m and derate the maximum ambient temperature by 1°C/100m.
(For 1500W models from 60V to 600V, derate either the output current or the ambient temperature, but not both.)
Any LEDs used in this product are Class 1 LEDs as per IEC 825-1
Regulatory Compliance:
EMC
Safety
Complies with the European EMC directive 89/336/EEC for Class A test and measurement products.
Complies with the Australian standard and carries the C-Tick mark.
This ISM device complies with Canadian ICES-001. Cet appareil ISM est conforme à la norme NMB-001 du Canada.
Electrostatic discharges >1kV near the I/O connectors may cause the unit to reset and require operator intervention.
Complies with the European Low Voltage Directive 73/23/EEC and carries the CE-marking.
Complies with the US and Canadian safety standards for test and measurement products.
Acoustic Noise Declaration:
Statements provided to comply with requirements of the German Sound Emission Directive, from 18 January 1991:
Sound Pressure Lp <70 dB(A), * At Operator Position, * Normal Operation, * According to EN 27779 (Type Test).
Schalldruckpegel Lp <70 dB(A) * Am Arbeitsplatz, * Normaler Betrieb, * Nach EN 27779 (Typprüfung).
Output Terminal Isolation:
6V to 60V units No output terminal may be more than +/- 60 VDC from any other terminal or chassis ground
80V to 600V units No output terminal may be more than +/- 600 VDC from any other terminal or chassis ground
AC Input:
Nominal Input
Input Current 750W
Input Current 1500W
Input Range
Power Factor
Efficiency
Inrush Current
100 – 240 VAC; 50/60Hz
10.5A @ 100 VAC nominal; 5A @ 200 VAC nominal
21A @ 100 VAC nominal; 11A @ 200 VAC nominal
85 – 265 VAC; 47 – 63 Hz.
0.99 at nominal input and rated output power
76% – 87% for 750W units; 77% – 88% for 1500W units
< 25A for 750W units; < 50 A for 1500W units