Hobart Welding Products 452 Welder User Manual


 
OM-222 Page 19
3-11. Electrical Service Guide
60 Hertz Models 300 Amp Model 450 Amp Model 650 Amp Model
Input Voltage 200 230 460 575 200 230 460 575 230 460 575
Input Amperes At Rated Output 70 61 31 25 102 89 45 36 124 62 50
Max Recommended Standard Fuse
Rating In Amperes
1
Time-Delay
2
80 70 35 30 125 110 50 45 150 70 60
Normal Operating 3 110 90 45 35 150 125 70 50 175 90 70
Min Input Conductor Size In AWG/
Kcmil
6 8 10 12 4 4 8 10 3 8 8
Max Recommended Input Conductor
Length In Feet (Meters)
149
(45)
131
(40)
356
(108)
342
(104)
136
(41)
180
(55)
319
(97)
335
(102)
144
(44)
210
(64)
328
(100)
Min Grounding Conductor Size In
AWG/Kcmil
6 8 10 12 6 6 8 10 6 8 8
Reference: 1999 National Electrical Code (NEC)
1 Consult factory for circuit breaker applications.
2 Time-Delay fuses are UL class RK5 .
3 Normal Operating (general purpose - no intentional delay) fuses are UL class K5 (up to and including 60 amp), and UL class H ( 65 amp and
above).
50 Hertz Models
300 Amp Model
450 Amp Model 650 Amp Model
Input Voltage 380 400 440 380 400 440 380 400 440
Input Amperes At Rated Output 35 33 31 54 51 47 75 71 65
Max Recommended Standard Fuse Rating In
Amperes
1
Time-Delay
2
40 40 35 60 60 50 90 80 80
Normal Operating 3 60 50 50 80 80 70 125 110 100
Min Input Conductor Size In AWG/Kcmil 10 10 10 8 8 8 6 6 6
Max Recommended Input Conductor Length
In Feet (Meters)
243
(74)
269
(82)
326
(99)
218
(66)
241
(73)
292
(89)
219
(67)
242
(74)
293
(89)
Min Grounding Conductor Size In AWG/Kcmil 10 10 10 8 8 8 6 6 8
Reference: 1999 National Electrical Code (NEC)
1 Consult factory for circuit breaker applications.
2 Time-Delay fuses are UL class RK5 .
3 Normal Operating (general purpose - no intentional delay) fuses are UL class K5 (up to and including 60 amp), and UL class H ( 65 amp and
above).