OM-314 Page 13
2-8. Electrical Service Guide
60 Hertz Models With Power Factor Correction Without Power Factor Correction
Input Voltage
200 230 460 575 200 230 460 575
Input Amperes At Rated Output
78 68 34 27 103 90 45 36
Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes
125 100 50 40 150 125 70 50
Min Input Conductor Size In AWG/Kcmil
8 8 12 14 6 8 10 12
Max Recommended Input Conductor Length
In Feet (Meters)
61 (19) 80 (25)
131
(40)
133
(40)
87 (27) 77 (23)
208
(64)
200
(61)
Min Grounding Conductor Size In AWG/Kcmil
8 8 12 14 6 8 10 12
Reference: 1993 National Electrical Code (NEC) S-0092-J
50 Hertz Models With Power Factor Correction
Without Power Factor
Correction
Input Voltage
220 260 380 440 520 220 380 440
Input Amperes At Rated Output
68 57 39 34 29 84 49 42
Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes
100 90 60 50 45 125 70 60
Min Input Conductor Size In AWG/Kcmil
8 8 10 12 12 8 10 10
Max Recommended Input Conductor Length
In Feet (Meters)
79 (24) 110 (33)
157
(48)
128
(39)
179
(55)
76 (23)
153
(47)
205
(63)
Min Grounding Conductor Size In AWG/Kcmil
8 8 10 12 12 8 10 10
Reference: 1993 National Electrical Code (NEC) S-0092-J