Hobart Welding Products OM-950 Welder User Manual


 
OM-950 Page 15
4-6. Weld Output Cables
For weld output cable replacements or extensions, contact your Factory
Authorized Service Agent.
NOTE
4-7. Electrical Service Guide
50/60 Hz
Single
Phase
Input Voltage 230
Input Amperes At Rated Output 47.5
Max Recommended Standard Fuse Rating In Amperes
Circuit Breaker
1
, Time-Delay
2
50
Normal Operating
3
70
Min Input Conductor Size In AWG
4
12
Max Recommended Input Conductor Length In Feet (Meters) 87 (26)
Min Grounding Conductor Size In AWG
4
12
Reference: 2005 National Electrical Code (NEC) (including article 630)
1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.