8-4. Generator Power Receptacles (Export Models)
. Generator power is not affected by weld
output.
1 130 V 32 A AC Receptacle RC1
2 220 Volt 16 A AC Receptacle RC2
3 130 Volt 16 A AC Receptacle RC3
Receptacles supply 60 Hz single-phase
power at weld/power speed.
4 Supplementary Protector CB1
5 Supplementary Protectors CB2 And
CB3
CB1 protects RC1 and the generator wind-
ing from overload. If CB1 opens, RC1 and
RC2 do not work. Place switch in On position
to reset.
CB2 protects RC2, and CB3 protects RC3
from overload. If a supplementary protector
opens, the receptacle does not work. Place
switch in On position to reset.
. If a supplementary protector continues
to open, contact Factory Authorized
Service Agent.
Maximum output is 4 kVA/kW from RC1 and
2.2 kVA/kW from RC2 or RC3. Maximum
output from all receptacles is 4 kVA/kW.
Combined output of receptacles is limited to
4 kVA/kW output of generator. If maximum
output is exceeded, auxiliary equipment will
stop or not run properly.
EXAMPLE: If 20 A is drawn from RC1, only
8 A is available at each of the other
receptacles.
(110 V x 20 A) + ( 110 V x 8 A) + (110 V x 8
A) = 4 kVA/kW.