MX60 is not equalizing
• Has the EQ cycle been initiated?
In the EQ Menu, press START to begin process. When the EQ cycle has been initiated,
“EQ-MPPT” will be displayed.
• The EQ cycle has been initiated, but the battery is not equalizing.
The EQ cycle will begin when the target EQ set point voltage has been reached. A small ar
ray or cloudy weather will delay the EQ cycle. Accordingly, running too many AC and/or DC loads
will delay the EQ cycle, too.
• An EQ set point that is too high relative to the battery voltage will delay the EQ cycle.
• If the PV array voltage is close to the battery voltage, the panels could be warm/hot causing the
Maximum Power Point to be at or lower than the battery voltage which can delay the EQ cycle.
MX60 Sweeping frequently
• A short sweep interval time will cause the MX60 to sweep frequently. A sweep interval of seven
to ten minutes is recommended.
• When the current limit set point is achieved, the MX60 will continue to sweep to maintain the
targeted current limit.