Outback Power Systems Systems Battery Charger User Manual


 
28
l
OutBack Power Systems Inc. 2005
Off-Grid Specifications Sealed Models Vented Models
FX2012T FX2524T FX3048T VFX2812 VFX3524 VFX3648
Nominal DC Input Voltage 12 VDC 24 VDC 48 VDC 12 VDC 24 VDC 48 VDC
Continuous Power Rating at 25° C 2000 VA 2500 VA 3000 VA 2800 VA 3500 VA 3600 VA
AC Voltage/Frequency 120 VAC 60 Hz 120 VAC 60 Hz 120 VAC 60 Hz 120 VAC 60 Hz 120 VAC 60 Hz 120 VAC 60 Hz
Continuous AC RMS Output at 25° C 17.0 amps AC 20.8 amps AC 25.0 amps AC 23.3 amps AC 29.2 amps AC 30.0 amps AC
Idle Power Full ~ 20 Watts ~ 20 Watts ~ 23 Watts ~ 20 Watts ~ 20 Watts ~ 23 Watts
Search ~ 6 Watts ~ 6 Watts ~ 6 Watts ~ 6 Watts ~ 6 Watts ~ 6 Watts
Typical Efficiency 90% 92% 93% 90% 92% 93%
Total Harmonic Distortion Typical 2% 2% 2% 2% 2% 2%
Maximum 5% 5% 5% 5% 5% 5%
Output Voltage Regulation ± 2% ± 2% ± 2% ± 2% ± 2% ± 2%
Maximum Output Current Peak 56 amps AC 70 amps AC 70 amps AC 56 amps AC 70 amps AC 70 amps AC
RMS 40 amps AC 50 amps AC 50 amps AC 40 amps AC 50 amps AC 50 amps AC
AC Overload Capability Surge 4800 VA 6000 VA 6000 VA 4800 VA 6000 VA 6000 VA
5 Second 4000 VA 4800 VA 4800 VA 4000 VA 5000 VA 5000 VA
30 Minutes 2500 VA 3200 VA 3200 VA 3200 VA 4000 VA 4000 VA
AC Input Current Maximum 60 amps AC 60 amps AC 60 amps AC 60 amps AC 60 amps AC 60 amps AC
AC Input Voltage Range (MATE Adjustable) 80 to 150 VAC 80 to 150 VAC 80 to 150 VAC 80 to 150 VAC 80 to 150 VAC 80 to 150 VAC
AC Input Frequency Range 54 to 66 Hz 54 to 66 Hz 54 to 66 Hz 54 to 66 Hz 54 to 66 Hz 54 to 66 Hz
DC Input Voltage Range 10.5 to 17.5 VDC 21.0 to 34.0 VDC 42.0 to 68.0 VDC 10.5 to 17.0 VDC 21.0 to 34.0 VDC 42.0 to 68.0 VDC
Continuous Battery Charge Output 80 amps DC 55 amps DC 35 amps DC 125 amps DC 85 amps DC 45 amps DC
Minimum Recommended DC Breaker OBDC-250 OBDC-175 OBDC-100 OBDC-250 OBDC-250 OBDC-175
Warranty Standard 2 year / Optional 5 year Standard 2 year / Optional 5 year
Weight Unit 62.6 lbs (28.4 kg) 61 lbs (27.7 kg)
Shipping 67 lbs (30 kg) 64 lbs (29 kg)
Dimensions (H x W x L) Unit 13 x 8.25 x 16.25” (33 x 21 x 41 cm) 12 x 8.25 x 16.25” (30 x 21 x 41 cm)
Shipping 21.75 x 13 x 22” (55 x 33 x 56 cm) 21.75 x 13 x 22" (55 x 33 x 56 cm)
Grid-Interactive Specifications Sealed Models Vented Models
GTFX2524 GTFX3048 GVFX3524 GVFX3648
Nominal DC Input Voltage 24 VDC 48 VDC 24 VDC 48 VDC
Continuous Power Rating at 25° C 2500 VA 3000 VA 3500 VA 3600 VA
AC Voltage/Frequency 120 VAC 60 Hz 120 VAC 60 Hz 120 VAC 60 Hz 120 VAC 60 Hz
Continuous AC RMS Output at 25° C 20.8 amps AC 25.0 amps AC 29.2 amps AC 30.0 amps AC
Idle Power Full ~ 20 Watts ~ 20 Watts ~ 20 Watts ~ 20 Watts
Search ~ 6 Watts ~ 6 Watts ~ 6 Watts ~ 6 Watts
Typical Efficiency 92% 93% 92% 93%
Total Harmonic Distortion Inverting 2% 2% 2% 2%
Selling < 5% < 5% < 5% < 5%
Output Voltage Regulation ± 2% ± 2% ± 2% ± 2%
Maximum Output Current Peak 70 amps AC 70 amps AC 70 amps AC 70 amps AC
RMS 50 amps AC 50 amps AC 50 amps AC 50 amps AC
AC Overload Capability Surge 6000 VA 6000 VA 6000 VA 6000 VA
5 Second 4800 VA 4800 VA 5000 VA 5000 VA
30 Minutes 3200 VA 3200 VA 4000 VA 4000 VA
AC Input Current Maximum 60 amps AC 60 amps AC 60 amps AC 60 amps AC
AC Input Voltage Range (MATE Adjustable) 80 to 150 VAC 80 to 150 VAC 80 to 150 VAC 80 to 150 VAC
AC Input Frequency Range 58 to 62 Hz 58 to 62 Hz 58 to 62 Hz 58 to 62 Hz
DC Input Range 21.0 to 34.0 VDC 42.0 to 68.0 VDC 21.0 to 34.0 VDC 42.0 to 68.0 VDC
Continuous Battery Charge Output 55 amps DC 35 amps DC 85 amps DC 45 amps DC
Minimum Recommended DC Breaker OBDC-175 OBDC-100 OBDC-250 OBDC-175
Warranty Standard 2 year / Optional 5 year Standard 2 year / Optional 5 year
Weight Unit 62.6 lbs (28.4 kg) 61 lbs (27.7 kg)
Shipping 67 lbs (30 kg) 64 lbs (29 kg)
Dimensions (H x W x L) Unit 13 x 8.25 x 16.25” (33 x 21 x 41 cm) 12 x 8.25 x 16.25” (30 x 21 x 41 cm)
Shipping 21.75 x 13 x 22” (55 x 33 x 56 cm) 21.75 x 13 x 22" (55 x 33 x 56 cm)
4