Philips 380-400-415V Work Light User Manual


 
OEM Catalogue 2009/20103.124
HID-DynaVision Control SON
Electrical installation notes
Mains operation
Rated mains voltage 220 - 240 V
With tolerances for performance 203 - 254 V
With tolerances for operation 180 - 264 V
Mains frequency 50/60 Hz
Operation frequency (typical) 50 Hz
Power factor* (nominal power) > 0.92
Power factor* (35% power) > 0.7
* With rated PF capacitor value
Earth leakage current (per gear) < 0.5 mA
Overvoltage protection 48 hrs at 325 Vac
2 hrs at 366 Vac
5 min at 400 Vac
Cable length to normal gear No limit.
Notes:
1. With three-phase mains supply, neutral should never be
disconnected; otherwise circuitry could be damaged.
2. Gear must be earthed.
3. Power factor correction capacitor should be connected directly
on the mains; when installing this device in front of existing gear, the
original capacitor has to be removed.
Control characteristics
Control input
Control voltage input 1-10 V
Protected against mains voltage
connection
Yes
Control resistance (to be
connected on 1-10V input)
0-100kΩ
Regulating light level SON
250/400 W
20 - 100%
After ignition or lamp restrike allways 100% level for 5 min
Gear dimming fading rates are:
SON 250/400 W
Fade up (35-100%) < 1.0 min
Fade down (100-35%) < 1.5 min
Mechanical installation notes
Wire cross-section:
On the mains side 0.75…2.5 mm
2
On the lamp side 0.75…2.5 mm
2
Strip length 6 mm
HID-DVC