11
SANYO’s Mini ECOi is suited
for numerous commercial and
premium residential applications.
SANYO OUTDOOR
CHXSERIES
Mini ECOi Multi Split VRF Heat Pump
CHX (R) 03652 / CHX (R) 05252
KEY FEATURES:
* Single Phase 208/230 volts
* One Outdoor Unit Connects As Many As 9 Indoor Units
(50%-130% ratio of indoor to outdoor capacity)
* Inverter Driven Twin Rotary Compressor
* Operating Range (Outdoor Ambient)
- Cooling 14 FDB to 113 FDB
- Heating -4 FWB to 59 FWB
* Ultra Quiet Operation As Low As 51dB(a)
* Variable Speed DC Fan Motor
* Piping:
-656 Feet - Maximum Total Liquid Line
-164 Feet - Maximum Vertical Between Indoor and Outdoor (Outdoor Above Indoor)
-131 Feet - Maximum Vertical Between Indoor and Outdoor (Outdoor Below Indoor)
* Defrost control, Reverse cycle, microprocessor control
* External finish: Galvanized steel plate with powder paint
* Refrigerant control: Electronic expansion valve
DESCRIPTION
CHX (R)
03652 CHX (R) 05252
POWER SOURCE
208-230V/1PH/60Hz 208-230V/1PH/60Hz
PERFORMANCE
COOLING CAPACITY
SEER
HEATING CAPACITY
HSPF
AIR CIRCULATION (HI)
Ducted Non-Ducted Mix
40,000 39,000 39,000 BTU/H
14.20 16.40 15.30
40,500 42,500 41,500 BTU/H
8.20 9.60 8.90
3,530 CFM
Ducted Non-Ducted Mix
51,500 52,000 51,500 BTU/H
14.6 17.3 16
57,500 58,000 58,500 BTU/H
7.7 9.5 8.6
3,530 CFM
ELECTRICAL RATINGS
VOLTAGE RATING
AVAILABLE VOLTAGE RANGE
RUNNING AMPERES
MAX. RUNNING AMPERES
POWER INPUT
MAX. POWER INPUT
MIN. CIRCUIT AMPACITY
MAX CIRCUIT AMPACITY
COOLING HEATING
208 / 230 V 208 / 230 V
187—253 V 187—253 V
14.6 / 13.6 A 14.6 / 13.6 A
23.6 / 23.6 A 23.6 / 23.6 A
2.76 / 2.76 Kw 2.88 / 2.88 Kw
4.85 / 4.85 Kw 4.85 / 4.85 Kw
18 A
30 A
COOLING HEATING
208 / 230 V 208 / 230 V
187—253 V 187—253 V
23.5 / 21.9 A 23.5 / 21.9 A
28 / 28 A 28 / 28 A
4.57 / 4.57 Kw 4.58 / 4.58 Kw
5.72 / 5.72 Kw 5.7 2 / 5.72 Kw
29 A
50 A
REFRIGERANT TUBING
LIMIT OF TUBING LENGTH
LIMIT OF ELEVATION DIFFERENCE
BETWEEN THE 2 UNITS
656 ft
Outdoor unit is higher than indoor unit: 164
Outdoor unit is lower than indoor unit: 131
656 ft
Outdoor unit is higher than indoor unit: 164
Outdoor unit is lower than indoor unit: 131
REFRIGERANT TUBE DIAMETER
LIQUID TUBE IN.
GAS TUBE IN.
3/8"
5/8"
3/8"
3/4"
UNIT DIMENSIONS
INCHES (") / LBS.
SHIPPING WEIGH / VOLUME
EXTERNAL AIR TEMP. OPERATION RANGE
Height/ Width/ Depth/ Net Weight
49”/ 37”/ 14”/ 229 lbs.
247 lbs. / 19.8 ft.
3
Cooling:14 to 113 (DB)/Heating: -4 to 59 (WB)
Height/ Width/ Depth/ Net Weight
49”/ 37”/ 14”/ 229 lbs.
247 lbs. / 19.8 ft.
3
Cooling:14 to 113 (DB)/Heating: -4 to 59 (WB)
* NOTE: *(R) in Model # indicates Salt Protection - Special Order