Sanyo ECOi Work Light User Manual


 
11
SANYO’s Mini ECOi is suited
for numerous commercial and
premium residential applications.
SANYO OUTDOOR
CHXSERIES
Mini ECOi Multi Split VRF Heat Pump
CHX (R) 03652 / CHX (R) 05252
KEY FEATURES:
* Single Phase 208/230 volts
* One Outdoor Unit Connects As Many As 9 Indoor Units
(50%-130% ratio of indoor to outdoor capacity)
* Inverter Driven Twin Rotary Compressor
* Operating Range (Outdoor Ambient)
- Cooling 14 FDB to 113 FDB
- Heating -4 FWB to 59 FWB
* Ultra Quiet Operation As Low As 51dB(a)
* Variable Speed DC Fan Motor
* Piping:
-656 Feet - Maximum Total Liquid Line
-164 Feet - Maximum Vertical Between Indoor and Outdoor (Outdoor Above Indoor)
-131 Feet - Maximum Vertical Between Indoor and Outdoor (Outdoor Below Indoor)
* Defrost control, Reverse cycle, microprocessor control
* External finish: Galvanized steel plate with powder paint
* Refrigerant control: Electronic expansion valve
DESCRIPTION
CHX (R)
03652 CHX (R) 05252
POWER SOURCE
208-230V/1PH/60Hz 208-230V/1PH/60Hz
PERFORMANCE
COOLING CAPACITY
SEER
HEATING CAPACITY
HSPF
AIR CIRCULATION (HI)
Ducted Non-Ducted Mix
40,000 39,000 39,000 BTU/H
14.20 16.40 15.30
40,500 42,500 41,500 BTU/H
8.20 9.60 8.90
3,530 CFM
Ducted Non-Ducted Mix
51,500 52,000 51,500 BTU/H
14.6 17.3 16
57,500 58,000 58,500 BTU/H
7.7 9.5 8.6
3,530 CFM
ELECTRICAL RATINGS
VOLTAGE RATING
AVAILABLE VOLTAGE RANGE
RUNNING AMPERES
MAX. RUNNING AMPERES
POWER INPUT
MAX. POWER INPUT
MIN. CIRCUIT AMPACITY
MAX CIRCUIT AMPACITY
COOLING HEATING
208 / 230 V 208 / 230 V
187—253 V 187—253 V
14.6 / 13.6 A 14.6 / 13.6 A
23.6 / 23.6 A 23.6 / 23.6 A
2.76 / 2.76 Kw 2.88 / 2.88 Kw
4.85 / 4.85 Kw 4.85 / 4.85 Kw
18 A
30 A
COOLING HEATING
208 / 230 V 208 / 230 V
187—253 V 187—253 V
23.5 / 21.9 A 23.5 / 21.9 A
28 / 28 A 28 / 28 A
4.57 / 4.57 Kw 4.58 / 4.58 Kw
5.72 / 5.72 Kw 5.7 2 / 5.72 Kw
29 A
50 A
REFRIGERANT TUBING
LIMIT OF TUBING LENGTH
LIMIT OF ELEVATION DIFFERENCE
BETWEEN THE 2 UNITS
656 ft
Outdoor unit is higher than indoor unit: 164
Outdoor unit is lower than indoor unit: 131
656 ft
Outdoor unit is higher than indoor unit: 164
Outdoor unit is lower than indoor unit: 131
REFRIGERANT TUBE DIAMETER
LIQUID TUBE IN.
GAS TUBE IN.
3/8"
5/8"
3/8"
3/4"
UNIT DIMENSIONS
INCHES (") / LBS.
SHIPPING WEIGH / VOLUME
EXTERNAL AIR TEMP. OPERATION RANGE
Height/ Width/ Depth/ Net Weight
49”/ 37”/ 14”/ 229 lbs.
247 lbs. / 19.8 ft.
3
Cooling:14 to 113 (DB)/Heating: -4 to 59 (WB)
Height/ Width/ Depth/ Net Weight
49”/ 37”/ 14”/ 229 lbs.
247 lbs. / 19.8 ft.
3
Cooling:14 to 113 (DB)/Heating: -4 to 59 (WB)
* NOTE: *(R) in Model # indicates Salt Protection - Special Order