Sanyo ECOi Work Light User Manual


 
15
SANYO OUTDOOR
WCHDXSERIES
W 2-Way ECOi VRF Heat Pumps combined units
DESCRIPTION
WCHDX
14463 WCHDX 16863 WCHDX 19263
PERFORMANCE
COOLING CAPACITY: BTU/H
POWER INPUT: KW
HEATING CAPACITY: BTU/H
POWER INPUT: KW
includes (2) CHDX07263
144,000
10.56
162,000
11.58
includes (1) CHDX07263 and
(1) CHDX09663
168,000
12.97
189,000
14.39
includes (2) CHDX09663
192,000
15.38
216,000
17.2
COOLING MODE NOMINAL CONDITIONS
INDOOR: °F WB/ °F DB
OUTDOOR: °F DB
PIPE LENGTH: FEET
LEVEL DIFFERENCE: FEET
80/67
95
25
0
80/67
95
25
0
80/67
95
25
0
HEATING MODE NOMINAL CONDITIONS
INDOOR: °F DB
OUTDOOR: °F DB/ °F WB
PIPE LENGTH: FEET
LEVEL DIFFERENCE: FEET
70
47/43
25
0
70
47/43
25
0
70
47/43
25
0
OPERATING RANGE
COOLING: °F DB
HEATING: °F WB
14 to 113
-4 to 59
14 to 113
-4 to 59
14 to 113
-4 to 59
COMPRESSOR
TYPE/QUANTITY
CAPACITY CONTROL RANGE: %
2 Inverter driven Rotary
6 - 100%
2 Inverter driven Rotary
& 1 fixed speed scroll
6-100%
2 Inverter driven Rotary
& 2 fixed speed scroll
6-100%
FAN
TYPE/QUANTITY
FAN MOTOR OUTPUT: (KW)
EXTERNAL STATIC PRESSURE
1 Propeller (ea)
0.7 kW (ea)
.04 / .25
1 Propeller (ea)
0.7 kW (ea)
.04 / .25
1 Propeller (ea)
0.7 kW (ea)
.04 / .25
POWER SUPPLY
V/PH/HZ
MINIMUM CIRCUITS AMPS (MCA): (A)
MAX. OVERCURRENT PROTECTION (MOCP): (A)
208 - 230/ 3/ 60
52
80
208 - 230/ 3/ 60
60
85
208 - 230/ 3/ 60
68
90
WEIGHT: (LBS)
1168 1267 1366
COIL:
COIL FACE AREA:(SQ. FT.)
NUMBER OF ROWS:
29.5(ea)
4(ea)
29.5(ea)
4(ea)
29.5(ea)
4(ea)
PROTECTION DEVICES
HIGH PRESSURE SWITCH/OVERCURRENT
(CT METHOD)
CRANKCASE HEATERS:(W)
Yes
25 + 25
Yes
25 + 25 + 32
Yes
25 + 32 X 2
* NOTE: *460 Volt Step Down Transformers (460-230) available for 6 and 8 ton condensers
EACH OUTDOOR UNIT REQUIRES A SEPARATE
ELECTRICAL FUSED DISCONNECT, SEE INDIVIDUAL
OUTDOOR REQUIREMENTS.
(R) indicates with salt protection - Special Order