Sanyo ECOi Work Light User Manual


 
MODELS
(Type: Nominal Cooling Capacity, etc)
Volt PH
CHDZ 07263
72,000 BTU Heat Recovery 208-230V/60 HZ 3
CHDZ R07263
72,000 BTU Heat Recovery
With Salt Protection - Special Order
208-230V/60 HZ 3
CHDZ 09663
96,000 BTU Heat Recovery 208-230V/60 HZ 3
CHDZ R09663
96,000 BTU Heat Recovery
With Salt Protection - Special Order
208-230V/60 HZ 3
CHDZ 07263 / CHDZ (R)07263
CHDZ 09663 / CHDZ (R)09663
KEY FEATURES:
* “ECO Friendly” R410A Refrigerant
* Heat Recovery system simultaneous heating-cooling
* One Outdoor Unit Connects As Many As 17 Indoor Units
(50%-130% ratio of indoor to outdoor capacity)
* Heat Pump
* One Outdoor Unit Connects As Many As 17 Indoor Units
(50%-130% ratio of indoor to outdoor capacity)
* CHDZ07263 includes one inverter driven Rotary compressor
* CHDZ09663 includes one inverter driven Rotary compressor
and one AC Constant Speed Scroll Compressor
* Operating Range (Outdoor Ambient)
- Cooling 14 FDB to 113 FDB
- Heating -4 FWB to 59 FWB
* Ultra Quiet Operation As Low As 51.5dB(a)
* Variable Speed DC Fan Motor (ESP adjustable to 0.25” wc)
* Flexible Piping Design:
- 984 Feet - Maximum Total Liquid Line
- 492 Feet - Maximum Outdoor To Most Distant Indoor Unit
- 164 Feet - Maximum Vertical Between Indoor and Outdoor
(Outdoor Above Indoor)
- 131 Feet - Maximum Vertical Between Indoor and Outdoor
(Outdoor Below Indoor)
SANYO’s ECOi Heat Recovery series offers
the ability to heat and cool different
zones simultaneously.
SANYO was the first manufacturer in the
world to develop this energy saving heat
recovery solution. Offering all the features
of our standard heat pump series, the 3-Way
solution can offer even higher energy savings
for the building owner.
* NOTE: *460 Volt Step Down Transformers (460-230) available for 6 and 8 ton condensers
06
CHDZSERIES
3-Way ECOi VRF Heat Recovery