Sanyo ECOi Work Light User Manual


 
SANYO OUTDOOR
09
WCHDZSERIES
3-Way ECOi VRF Heat Recovery Combined Units
DESCRIPTION
WCHDZ
14463 WCHDZ 16863 WCHDZ 19263
PERFORMANCE
COOLING CAPACITY: BTU/H
POWER INPUT: KW
HEATING CAPACITY: BTU/H
POWER INPUT: KW
includes (1) CHDZ07263
and (1) CHDZ07263
144,000
10.56
162,000
11.58
includes (1)CHDZ07263 and
(1) CHDZ09663
168,000
12.97
189,000
14.39
includes (1) CHDZ09663
and (1) CHDZ09663
192,000
15.38
216,000
17.2
COOLING MODE NOMINAL CONDITIONS
INDOOR: °F WB/ °F DB
OUTDOOR: °F DB
PIPE LENGTH: FEET
LEVEL DIFFERENCE: FEET
80/67
95
25
0
80/67
95
25
0
80/67
95
25
0
HEATING MODE NOMINAL CONDITIONS
INDOOR: °F DB
OUTDOOR: °F DB/ °F WB
PIPE LENGTH: FEET
LEVEL DIFFERENCE: FEET
70
47/43
25
0
70
47/43
25
0
70
47/43
25
0
OPERATING RANGE
COOLING: °F DB
HEATING: °F WB
14 to 113
-4 to 59
14 to 113
-4 to 59
14 to 113
-4 to 59
COMPRESSOR
TYPE/QUANTITY
CAPACITY CONTROL RANGE: %
2 Inverter driven Rotary
6 - 100%
2 Inverter driven Rotary
& 1 fixed speed scroll
6 - 100%
2 Inverter driven Rotary
& 2 fixed speed scroll
6- 100%
FAN
TYPE/QUANTITY
FAN MOTOR OUTPUT: (KW)
EXTERNAL STATIC PRESSURE
1 Propeller (ea)
0.7 kW (ea)
.04 / .25
1 Propeller (ea)
0.7 kW (ea)
.04 / .25
1 Propeller (ea)
0.7 kW (ea)
.04 / .25
POWER SUPPLY
V/PH/HZ
MINIMUM CIRCUITS AMPS (MCA): (A)
MAX. OVERCURRENT PROTECTION (MOCP): (A)
208 - 230/ 3/ 60
52
80
208 - 230/ 3/ 60
60
85
208 - 230/ 3/ 60
68
90
WEIGHT: (LBS)
1168 1267 1366
COIL:
COIL FACE AREA:(SQ. FT.)
NUMBER OF ROWS:
29.5(ea)
4(ea)
29.5(ea)
4(ea)
29.5(ea)
4(ea)
PROTECTION DEVICES
HIGH PRESSURE SWITCH/OVERCURRENT
(CT METHOD)
CRANKCASE HEATERS:(W)
Yes
25 + 25
Yes
25 + 25 + 32
Yes
25 + 32 X 2
* NOTE: *460 Volt Step Down Transformers (460-230) available for 6 and 8 ton condensers
EACH OUTDOOR UNIT REQUIRES A SEPARATE ELECTRICAL FUSED DISCONNECT,
SEE INDIVIDUAL OUTDOOR REQUIREMENTS.
(R) indicates with salt protection - Special Order