Studer Innotec HPC 2800-12, HPC 4400-24, HPC 600-48, HPC 6000-48 Battery Charger User Manual


 
STUDER INNOTEC HP-COMPACT
HP-COMPACT V5.4 8/80
connection between Neutral and earth in inverter mode only may be done by
installing a bridge internally to the unit. Please contact your installer regarding this
point.
(2) Remote control for remote adjustment of the input limit. (see chap. 4.6.3)
2.2 Description of the main functions
2.2.1 The inverter
The sine wave inverter HP-COMPACT generates a sinusoidal AC voltage with an
exceptionally precise voltage and stabilized frequency. In order to start large electric
motors, the user has the possibility to use a short surge power which is 3 times the
nominal power of the HP-COMPACT.
The inverter is protected against overload and short circuit. A power stage with the
latest MOS-FET power transistors, a toroidal transformer, and a fast regulating
system makes a robust and reliable inverter with the highest efficiency. A 1-20 Watt
adjustable charge detection system allows the smallest energy consumption and
ensures a long life for the battery.
2.2.2 The transfer system
HP-COMPACT can be connected to an AC source. For example a stand-by
emergency generator or the AC network. With the transfer system, on one side you
have an alternating voltage at the output for the use of consumer appliances. On the
other side the battery park is being charged. The distribution of energy between the
consumer appliances and battery charger is automatic.
2.2.3 The battery charger
The built-in battery charger is so designed that it can charge the battery quickly and
fully. A microprocessor controlled, Step charging process, ensures the optimal
charging of the battery. The desired charging current can be set continuously from 0
to 70/90/100/110 A, as per the model. The setting is made accordingly to the battery
capacity and power available.
The battery charger is designed for lead-acid and lead-gel batteries. Thanks to the
floating charge system the batteries can remain continuously connected.
2.2.4 Remote control
As an option, a remote control RCC-01 can be connected to HP-COMPACT. All
operating features and displays, save the adjustment levels (22/23/24/26), are
available on the re-mote control. It is supplied with a 20m long cable. This cable can
be up to 40m long. On the remote control, output power and charging current are
also displayed.
2.2.5 Remote control for Power Sharing
This remote control RPS-01 can be connected to the HP-COMPACT in the gland for
the temperature sensor. The maximum current available from the energy source can
be adjusted by the turning button.