HP-COMPACT V5.4 10/80
3 Mounting and installing
3.1 Installation place
The location of the HP-COMPACT must be driven by the following criteria:
Protection from unauthorized handling
Dry dust free room, no condensation
Never install directly over the battery and never in a cabinet together with the
batteries
Keep ventilation holes free
In mobile installations it is important to keep the vibrations down as low as
possible
3.2 Fixing
Basically the HP-COMPACT can be installed in any desired location but only
vertically. First of all the plate supplied along with the HP-COMPACT must be
screwed firmly (due to the weight of the device) on the wall. Then the HP-COMPACT
is hooked on the plate and screwed underneath.
Cautious: the fixing must be fully made otherwise the HP-COMPACT may fall
and cause important damages.
In motor vehicles HP-COMPACT must be fixed on vibrations reducing elements. The
HP-COMPACT must not be fixed on a combustible base, as the back of the casing
can get hot and reach up to 60 degrees Celsius.
3.3 Connections
3.3.1 General instructions on connecting
The cable connection on the terminals AC INPUT and AC OUTPUT must be
carried out with a screwdriver Nr.3 and the connection of the AUX RELAY
terminal with a screwdriver Nr.2.
The conductor cross section on the terminals AC INPUT / AC OUTPUT / must
comply with the local rules.
All connecting cables and also the battery cables must be fixed with strain relief
clamps.
The fuses supplied with the HPC 4400-24, 6000-48 and 8000-48 have to be
installed (see description in 3.4). The cable cross section for the HP 2800-12,
4400-24, 6000-48 and 8000-48 is resp. 95, 70, 50 and 70 mm2 and their length
must be as short as possible (max. 2m).
The fuse supplied with the product (save for HPC 2800-12) does not protect the
battery cables.
To protect the battery cables, a fuse corresponding to the conductor cross
section must be fixed directly on to the battery.
All cables must be tightly screwed in place. For safety, a yearly control is
recommended. In mobile installations controls must be carried out more often.
Connecting must be done by qualified people. Material such as cable,
connectors and distribution boxes, fuses etc. used in the installation must
comply with the respective valid low-voltage installation rules and regulations in
force.
3.3.2 Protection cover of the terminals connections
The protection cover must to be closed after any service on the appliance.
3.4 Connection Plan