Tripp Lite APINT Series Welding System User Manual


 
10A
AC Input/Output Connection
To avoid overloading your Inverter/Charger, be sure to match the power requirements of the equipment you plan to run at any one time (add their
total watts) with the output wattage capacity of your Inverter/Charger model. When figuring the power requirements of your equipment, do
not confuse “continuous” wattage with “peak” wattage ratings. Most electric motors require extra power at start-up (“peak” wattage) than
required to run continuously after start-up, sometimes over 100% more. Some motors, such as in refrigerators and pumps, start and stop
intermittently according to demand, requiring “peak” wattage at multiple, unpredictable times during operation.
Connection for Models with Cords and Receptacles
With a user-supplied cable and country-specific plug, connect the Inverter/Charger's IEC-320 AC Input Receptacle to your utility wall out-
let. Connect your equipment directly to the Inverter/Charger's IEC-320 AC Output Receptacle(s). Select models also include a Universal
AC Output Adapter which allows you to connect equipment with a wide variety of plug styles.
Warning! Consult a qualified electrician and follow all applicable electrical codes
and requirements for hardwire connection. Disconnect both DC input and AC utility
supply before attempting hardwiring.
Connection for Models with Hardwire Terminals
Remove the screws and cover plate over the hardwire terminal box. Remove the knockout covers closest to the desired electrical source and
to your equipment. Attach 1.28 cm diameter conduits (user-supplied) to the knockouts and thread wires through. Connect the conduits to
each other with the ground bond connection supplied.
OUTPUT/NEUTRAL
OUTPUT/HOT
GROUND
INPUT/NEUTRAL
INPUT/HOT
“FOR USE WITH COPPER WIRE ONLY”
Ground*
Connect the incoming and outgoing ground wires to the
ground (green) terminal .
AC Input
Connect the incoming hot wire to the input hot
(brown) terminals .
Connect the incoming neutral wire to the input neutral (blue)
terminal .
AC Output
Connect the outgoing hot wire to the output hot
(black) terminal .
Connect the outgoing neutral wire to the output neutral (white)
terminal .
Replace cover plate and tighten screws.
* If the incoming conduit only contains two wires (hot and neutral), the incoming conduit must
be bonded to the main ground lug on the unit. In any case, the incoming conduit must be bond-
ed to earth or vehicle ground, and the incoming conduit must be bonded to the outgoing con-
duit.
5
1
2
3
4
5
DoubleBoost
Feature
Tripp Lite Inverter/Chargers deliver up to twice their nameplate
rated wattage for up to 10 seconds,* providing the extra power
needed to cold start heavy-duty tools and equipment.
OverPower
Feature
Tripp Lite Inverter/Chargers deliver up to 150% of their name
plate rated wattage for up to 1 hour,* providing plenty of reserve
power to reliably support tools and equipment longer.
* Actual duration depends on battery age, battery charge level and ambient temperature.
4
1
3
2