4 WATLOW DIN-A-MITE Style D User’s Manual
After removing all power, use a 7/16-inch nut driver to remove
fuse mounting nuts. Torque to 4.52 Nm (40 in-lb).
ç WARNINGS:
Ó 1 WARNING: Use National Electric (NEC) or other
country-specific standard wiring practices to install
and operate the DIN-A-MITE. Failure to do so may
result in damage to equipment and property,
and/or injury or loss of life.
Ó 2 WARNING: Wiring examples show L2 in phase-to-
phase, 200VÅ (ac) and above configuration. In
phase-to-neutral, 100VÅ (ac) and above
applications, L2 is neutral and must not be fused
or switched. Failure to follow this guideline could
result in personal injury or death.
Ó3 WARNING: Only authorized and qualified personnel
should be allowed to install and perform
preventive and corrective maintenance on this
unit. Failure to do so could result in damage to
equipment, and personal injury or death.
Ó
4
WARNING: Do not use the DIN-A-MITE Vac-input
models with a temperature controller that includes
an RC snubber circuit across its output. Remove
the RC snubber circuit before placing the DIN-A-
MITE into service.
5
WARNING: Hot surface, do not touch the heat sink.
Failure to follow this guideline could result in
personal injury.
ç
Ó
3
System Wiring Example
ç
Ó
3
Fuse Replacement