Xantrex Technology 25 Battery Charger User Manual


 
28
FUSE HOLDER
FUSE
BATTERY
CABLE
INVERTER
CABLE
FLAT WASHER
NUT
LOCK WASHER
COMPRESSION / RING TERMINAL
INSTALLATION
Improper stack up of hardware will cause
excessive heat and fuse failure. Stack up
as shown.
WARNING
EXPLODED VIEWS
OF FUSE ASSEMBLY
Battery Cable Fusing
A fuse is required by the NEC to protect
the battery and cables. A UL Listed DC rated
slow blow fuse must be installed in the positive
(+) battery cable, within 72 inches of the
battery or within 7 inches of a positive bus or
switch.
Recommended Fuse: UL Listed Class T
JLLN with a DC Rating. This fuse with fuse
holder is available from your dealer or Xantrex.
For Freedom 10 & 15
200 amp Fuse & Holder PN# 84-4155-00 (C/R)*
200 amp Fuse & Holder PN# 84-4158-00 (R/R)**
200 amp Fuse Only PN# 84-4157-00
For Freedom 20, 25, & 30
300 amp Fuse & Holder PN# 84-4156-00 (C/R)*
300 amp Fuse & Holder PN# 84-4154-00 (R/R)**
300 amp Fuse Only PN# 84-4151-00
* Compression / Ring Terminal
** Ring / Ring Terminal
FUSE HOLDER
FUSE
BATTERY
CABLE
INVERTER
CABLE
FLAT WASHER
LOCK WASHER
NUT
RING / RING TERMINAL
HARDWARE STACK-UP OPTIONS
+ (red)