Xantrex Technology XC2524 Battery Charger User Manual


 
Equalizing Flooded Batteries
975-0187-01-01 3–9
Performing An Equalization
Turn off or disconnect all DC loads on the battery during equalization. The voltage
applied to the battery during equalization may be above the safe levels for some
loads.
To equalize your batteries:
1. Check the battery electrolyte level. If necessary, refill with distilled water only.
All the cells should have similar electrolyte levels. If the levels are widely
different, it will influence the relative concentration of acid, thereby affecting
the specific gravity measurements.
2. Verify that all banks are in either float or rest mode.
3. Press
MODE and BANK at the same time.
4. Press
BANK to select which bank you wish to equalize. The bank indicator light
will flash to show which bank has been selected.
5. Press and hold
ON/STANDBY to put the XC Series into equalization mode.
You can cancel the equalization request by pressing ON/STANDBY once.
If the battery cannot be equalized, the display will show .
Check that the battery is flooded and in float mode.
6. When the charger is in equalize mode, the display will show
.
7. Monitor the specific gravity of each cell of the battery during equalization with
a battery hydrometer.
The equalize cycle will terminate in one hour.
Check the specific gravity of each cell and repeat the equalization cycle until
they all meet the battery manufacturer’s specifications for specific gravity or
until the specific gravity stabilizes relative to each other for an hour.
8. The charger automatically exits equalization to float mode or rest mode after 1
hour. To manually exit equalization mode early, press
MODE and BANK at the
same time and then press and hold ON/STANDBY.
You can cancel the manual exit request by pressing ON/STANDBY once.
9. When equalization has finished, check the battery electrolyte level. If
necessary, refill with distilled water only.
XC_Charger_Owner.book Page 9 Friday, August 12, 2005 3:23 PM