Xantrex Technology XC2524 Battery Charger User Manual


 
Specifications
A–4 975-0187-01-01
Temperature Specifications
Protection Features
Nominal ambient 25 °C (77 °F)
Operating range 0 – 50 °C (32 – 122 °F)
Current de-rating approx. 2% (Imax) / °C (50 – 65 °C) (122 – 149 °F)
Storage -40 – 80 °C (-40 – 176 °F)
Humidity 5 – 95%, RH non-condensing
Battery reverse polarity No damage incurred by reverse polarity.
Safe non-operating battery voltage 35 VDC maximum
Over-voltage limits The XC Series will stop charging any bank that has a
voltage greater than + 0.5 V over the temperature
compensated absorption voltage. It will restart when
this voltage is + 0.2 V.
Output current limit XC3012: 30 – 33 ADC
XC5012: 50 – 55 ADC
XC1524: 15 – 16.5 ADC
XC2524: 25 – 27.5 ADC
Over-temperature Internal charger temperature is measured. Unit shuts
down and restarts as follows:
Over-temperature shutdown at 75 °C (167 °F)
Over-temperature restart at 70 °C (158 °F)
Current derating in ambient
temperatures
Rated current to 50 °C (122 °F)
2%/ °C derating above 50 °C (122 °F)
Battery over-temperature
protection
Battery temperature, as sensed by the battery
temperature sensor (if installed), results in the
charger no longer charging the individual battery or
bank at a battery temperature of 55 °C (132 °F).
XC_Charger_Owner.book Page 4 Friday, August 12, 2005 3:23 PM