A SERVICE OF

logo

MG500-EU-EN v1.0 7/13
4
Features
InsulationResistanceTesting
Thisdigitalinsulationresistancetesterwillmeasureinsulationresistancefrom800kohmsto
500GohmsusingDynamicAutoranging technology.Testvoltagesrangefrom500Vto10kV
in500Voltsteps.ThisinstrumentalsoemploysanAutoDischargeutility.
DAR:DielectricAbsorptionRatioTesting
The
DielectricAbsorptionistheratiooftheInsulationResistance,measuredat60seconds,
dividedbytheInsulationResistancemeasuredat30seconds).
DAR=Resistancemeasuredat1minute/Resistancemeasuredat30seconds
PI:PolarizationIndexTesting
ThePolarizationIndexistheratiooftheInsulationResistancemeasured
at10minutes
dividedbytheInsulationResistancemeasuredat1minute.
PI=Resistancemeasuredat10minutes/Resistancemeasuredat1minute
AutomaticDischargeofCapacitiveandInductiveCircuits
Thisinstrumentwillautomaticallydischargeallcircuits,chargedbythetester,upon
completionofatest.The
dischargecanbeobservedontheinstrument’sbargraphdisplay.
AutomaticBatteryTest
WhentheinstrumentisfirstpoweredON,atestcircuitappliesaheavycurrentdrawonthe
batteriesforafewsecondsandmeasuresthevoltageinordertodeterminethecapacityof
thebatteries.Theresultis
shownonthedisplay.
NormalOperationModeConsiderations
ThisinstrumentusesDynamicCurrentAutorangingtechnology.Thebargraphwill
displaythevoltagethatisstressingtheinsulationduringthefirst30secondsofatestand
duringthedischargeofthecircuitsattheendofthetest.Thedisplaywillalsoshowthe
elapsedtimefromthestartofthetestandthetotaltime,evenafterthetestinghasstopped.
SupplementalFeatures
o InsulationResistanceautorangingonallVoltageranges
o AutomaticDARcalculation
o AutomaticPIcalculation
o EnerSave™Modeconservesbattery
energyduringInsulationResistancetesting
o Overloadprotection
o Lowbatteryindicator
o AutoOfffeature
o Warningofexternalvoltagepresence(>500VACorVDC)