Installing the Neutral Sensor
The neutral sensor is an electrical duplicate of the
phase sensor, including the taps. Therefore, when
taps (if provided) are changed on the phase sensors,
the taps on the neutral sensor must be similarly
changed. For kits with fixed phase sensors, be sure
to use the corresponding tap on the neutral sensor.
Mount the neutral sensor on the outgoing neutral
lead, normally in the equipment bus or cable com-
partment. Figure 29 shows mounting details for the
neutral sensor for AK-50 breakers, while Figure 30
covers AK-75 and AK-100 breakers.
Figure 29. Outline of the neutral sensor for AK-50 breakers.