Heatcraft Refrigeration Products 25006801 Air Compressor User Manual


 
10
Refrigeration Piping
1. Normally, any straight run of tubing must be supported in at least two locations near each end of the run. Long
runs require additional supports. The refrigerant lines should be supported and fastened properly. As a guide,
3/8 to 7/8 should be supported every 5 feet, 1-1/8 and 1-3/8 every 7 feet; and 1-5/8 and 2-1/8 every 9 to 10 feet.
2. When changing directions in a run of tubing, no corner should be left unsupported. Supports should be placed a
maximum of 2 feet in each direction from the corner.
3. Piping attached to a vibrating object (such as a compressor or compressor base) must be supported in such
a manner that will not restrict the movement of the vibrating object. Rigid mounting will fatigue the copper
tubing.
4. Do not use short radius ells. Short radius elbows have points of excessive stress concentration and are subject to
breakage at these points.
5. Thoroughly inspect all piping after the equipment is in operation and add supports wherever line vibration is
signicantly greater than most of the other piping. Extra supports are relatively inexpensive as compared to
refrigerant loss.
Line Insulation
After the nal leak test, refrigerant lines exposed to high
or low ambient conditions should be insulated to reduce
heat loss or gain and prevent the formation of ash gas
in the liquid lines. Suction lines should be insulated with
3/4" wall Armstrong “Armaex” or equivalent. Liquid lines
should also be insulated with 1/2-inch wall insulation or
better. The insulation located in outdoor environments
should be protected from UV exposure to prevent
deterioration of insulating value.
Figure 6. Example of
Pipe Support
Figure 7.