Heatcraft Refrigeration Products 25006801 Air Compressor User Manual


 
8
Refrigeration Piping And Line Sizing
Refrigeration Piping And Line Sizing
The system as supplied by Heatcraft Refrigeration Products, was thoroughly cleaned and dehydrated at the factory.
Foreign matter may enter the system by way of the evaporator to condensing unit piping. Therefore, care must
be used during installation of the piping to prevent entrance of foreign matter. Install all refrigeration system
components in accordance with applicable local and national codes and in conformance with good practice required
for the proper operation of the system. The refrigerant pipe size should be selected from the tables in Refrigeration
System Installation Manual, Part Number 25001201. The interconnecting pipe size is not necessarily the same size as
the stub-out on the condensing unit or the evaporator.
The following procedures should be followed:
(a) Do not leave dehydrated compressors or lter-driers on condensing units open to the atmosphere any longer
than is absolutely necessary.
(b) Use only refrigeration grade (ACR) copper tubing, properly sealed against contamination.
(c) Suction lines should slope 1/4” per 10 feet towards the compressor (in direction of ow).
(d) Suitable P-type oil traps should be located at the base of each suction riser to enhance oil return to the
compressor.
(e) For desired method of superheat measurement, a pressure tap should be installed in each evaporator suction
line in the proximity of the expansion valve bulb.
(f) When brazing refrigerant lines, an inert gas should be passed through the line at low pressure to prevent scaling
and oxidation inside the tubing. Dry nitrogen is preferred.
(g) Use only a suitable silver solder alloy on suction and liquid lines.
(h) Limit the soldering paste of ux to the minimum required to prevent contamination of the solder joint internally.
Flux only the male portion of the connection, never the female. After brazing, remove excess ux.
(i) Wrap expansion valves with wet rags during brazing to the liquid line.
CAUTION: If the temperature gets too high, these components may be damaged. Heat absorbing compounds
or wet rags must be used to protect the expansion valve when brazing to the refrigerant
piping/line connections, and the suction line sensor must be removed per above instructions.
(j) Do not use “bull head” tees. This will cause oil return problems and can cause poor performance.
(k) If isolation valves are installed at the evaporator, full port ball valves should be used.