Heatcraft Refrigeration Products 25006801 Air Compressor User Manual


 
20
Start-up Checklist
Date of Start-up
Location
CONDENSING UNIT
MODEL #
ELECTRICAL
Check Compressor Amps for COOLER and
FREEZER compressors. Should match
nameplate.
YES NO
PIPING
Is suction line trapped at the Cooler?
YES NO
Is suction line trapped at the Freezer?
YES NO
DRAIN LINES
Are drain lines sloped properly?
YES NO
Is drain line trapped outside the Cooler?
YES NO
Is drain line trapped outside the Freezer?
YES NO
Is heat tape wrapped along entire length of
the drain line in the Freezer?
YES NO
Is heat tape plugged in and heating the drain
line?
YES NO
INSULATION
Are Liquid lines fully insulated?
YES NO
Are Suction lines fully insulated?
YES NO
SYSTEM CHECKS
Check Compressor Superheat for the
COOLER (Should be between 20°F. & 30°F.)
YES NO
Check Compressor Superheat for the
FREEZER (Should be between 20°F. & 30°F.)
YES NO
•Force unit into a Defrost Check heater amps.
Should match nameplate amps.
YES NO
Check LPS Time Delay Relays. Should be
set at 1 minute for both the COOLER and
FREEZER.
YES NO
Check Low Pressure Switch on FREEZER. Should be set
at 0 psig Cut-out/10 psig Cut-in.
YES NO
Did FREEZER and COOLER cycle o on LPS at Set-point
Temperature?
YES NO
Is the sight glass free of bubbles?
YES NO
Are the COOLER and FREEZER fans at proper speeds?
YES NO
Check system for refrigerant leaks. Are there any
leaks on the COOLER, FREEZER, CONDENSING UNIT or
INTERCONNECTING PIPING?
YES NO
Check system piping for unusual vibration or noise. Is
there any unusual vibration or noise on the COOLER,
FREEZER, CONDENSING UNIT or INTERCONNECTING
PIPING?
YES NO