Heath Zenith 52-4477-8 Work Light User Manual


 
3
598-1285-00
Black
(Standard)
Wiring Diagram 1
White
Master
Wiring Diagram 2
Red
Wiring Diagram 3
Green
or Bare
Slave
OPTIONAL WIRING
is fixture is provided with a sensor rated for 500 Watts. Since the fixture is only rated 100 Watts, 400
Watts of additional lighting may be controlled by this sensor.
When determining what a fixture is rated for, do not simply look at the rating on the lamp in the
fixture. Look at the marking which specifies the maximum lamp wattage for which the fixture is
suitable.
Once you have selected the fixtures to be connected and determined their maximum ratings, add these
ratings up. For instance, if you have 3 fixtures rated 100 Watts, 150 Watts, and 75 Watts respectively,
you have a total load of 325 Watts.
Wiring Diagram 1 – When wiring to control a standard light xture: Strip the motion sensor’s
red wire and connect to the standard light’s black wire. Connect all white wires together. Total fixture
ratings must not exceed 500 Watts (4.1 A).
Wiring Diagram 2 – When wiring to control another motion sensing light xture (Master /
Slave): Strip the red wire in both light fixtures. Connect the red wire of the controlling (master)
fixture to the red and black wires of the controlled (slave) fixture. Connect all white wires together.
Total fixture ratings must not exceed 500 Watts (4.1 A).
Wiring Diagram 3 – When wiring so either motion light turns on the both motion lights
(Master / Master): Strip the red wire in both light fixtures. Connect the red wire of one fixture to
the red wire of the second fixture. Note: In most installations, an additional wire (same gage as exist-
ing house wire) will have to be installed in the house to connect the two fixtures as master / master.
Connect all white wires together and all black wires together. Total fixture ratings must not exceed
500 Watts (4.1 A).
Black
White
Green
or Bare
Red
Master Master
Red
Black
White
Green
or Bare