Hitachi MK-97RD6679-00 Tool Storage User Manual


 
(Unit: mm)
1220
G
DKC615
a *1
b
195
125 65
835 655
63
90
61.5
74 457
482
585
Floor cutout area for cables
Caster
Screw jack
Service clearance
G
Grid panel (over 450mm x 450mm)
*1
215
150
195 215
G
482
585
DKC615
457 74
61.5
65
125
1100
150
655 835 1050
3250
90 63
1100
c *1
10*
2
1050
575
601
Rear
Front
DKC515
200 or more
Figure 2-5 Service Clearance and Floor Cutouts: Two Racks
Notes:
1. Clearance (a+b) depends on the floor load rating and clearance (c). See Table 2-4 for floor load
rating and clearance requirements.
Allow clearance of 100 mm on both sides of the storage system when the stabilizer plate(s) are to
be attached after the storage system is installed. The stabilizer plates have dimensions (H x W x D)
of 74 mm x 500 mm x 220 mm or 2.9 inches x 19.6 inches x 8.6 inches.
When storage systems of the same type are to be installed adjacent to each other, the minimum
clearance between the storage systems is 100 mm.
2. When installing a second rack, be sure to leave a 10-mm space.
2-12 Installation Requirements
Hitachi Universal Storage Platform VM Installation Planning Guide