Hitachi MK-97RD6679-00 Tool Storage User Manual


 
Input Voltage and Input Frequency
Table 2-6 lists the input voltage and input frequency requirements for the
Universal Storage Platform VM.
Table 2-6 Input Voltage and Input Frequency Requirements
Frequency Input Voltages (AC) Conditions Tolerance(%)
60Hz ±2Hz 200V, 208V or 230V 1 Phase
2 Wire + Ground
+6% or -8%
50Hz ±3Hz 200V, 220V, 230V or 240V 1 Phase
2 Wire + Ground
+6% or -8%
Circuit Breakers and Plugs
The PDU plugs are appropriate for the power sources at the installation sites:
For installations within the U.S., the plugs are NEMA L6-30P, which are
rated as 30A and 250V and have two 16A circuit breakers with 20A trip
values.
For installations outside the U.S., the plugs are IEC 309, which are rated as
32A and 250V and have two 16A circuit breakers with 20A trip values.
2-18 Installation Requirements
Hitachi Universal Storage Platform VM Installation Planning Guide