Ingersoll-Rand 125-200 HP/90-160 KW Air Compressor User Manual


 
1 0 0
P S I
3.4 MAIN MENU
The MAIN MENU screen is the point from which
various operator functions can be accessed. Refer to
the reference diagram in Figure 3.2.1.
Each of the functions can be chosen by using the up
and down arrows to highlight it on the screen.
The controller will go to the highlighted function if the
SELECT button is pressed or will return to the
CURRENT STATUS screen if the STATUS button is
pressed.
STATUS
SELECT
Ready To Start
-MAIN MENU-
Operator Setpoints
Options
Sensor Calibration
Alarm History
Clock Functions
1 0 0
P S I
3.5 OPERATOR SETPOINTS
STATUS
MAIN MENU
SELECT
Ready To Start
-OPERATOR SETPOINTS-
Offline Pressure
103 PSI
Online Pressure
93 PSI
Setpoints are user-adjustable variables in the
controller logic that can be set using the OPERATOR
SETPOINTS screen.
The name and value of each of the setpoints listed
below can be seen on the screen by moving the list up
and down using the arrow buttons.
Setpoints associated with options are described in the
OPTIONS Section 3.6.
A setpoint’s value can be changed by first highlighting
the item and its value and pressing the SELECT
button to highlight just the value. When the value line is
highlighted by itself, the value can be adjusted using
the up and down arrow buttons. The CANCEL and
SET buttons appear at this time. Press the SET button
to enter the new value, or press the CANCEL button to
return to the value of the setpoint prior to using the
arrows. The displayed value will flash twice to indicate
it has been entered into the setpoint, and the pair of
setpoint item and value display lines will again be
highlighted together.
Operator set points can be exited by pressing the
STATUS or MAIN MENU buttons. If no buttons are
pressed within 30 seconds, the display will return to
the CURRENT STATUS screen.
OPERATOR SETPOINTS RANGE STEP UNIT
Lead/Lag Lead or Lag --- ---
Offline Pressure 75 to RATED +3 1 PSIG
Online Pressure 65 to OFFLINE - 10 1 PSIG
Lag Offset 0 to 45 1 PSIG
Mode of Operation MOD/ACS, ON/OFF LINE, --- ---
MODULATION ONLY
Max Modulation Pressure
Online + 10 to Offline + 7 1
PSIG
Stop Delay Time 10 to 60 1 SEC
Star-Delta Time* 5 to 20 1 SEC
(Screen) Contrast 0 to 10 1 ---
* Does not apply to automatic across the line starters.
20