Ingersoll-Rand 125-200 HP/90-160 KW Air Compressor User Manual


 
45
EXAMPLE 3
The operator selects an unloaded run time of 10 minutes
in the OPTION routine and starts the compressor.The
unit runs loaded 12 minutes and then unloads.
After 12 minutes of running, the 10 minute mandatory
run-time for timer “A” has been met but the compressor
must continue to run unloaded an additional 10 minutes
to satisfy timer “B”.
After 10 minutes of unloaded run time, the compressor is
stopped automatically and the total run time was 22
minutes.
5.10 REMOTE START/STOP
The remote start/stop option allows the operator to
control the compressor from a remote mounted start/stop
station.
Two different switches can be wired to the controller for
remote start/stop. (Refer to Electrical Schematic 8.1 for
wiring locations). The switches are customer supplied
and must be of momentary type. The stop switch
contacts are normally closed and the start switch
contacts are normally open.
When starting the compressor from the remote location,
the Start button must be held depressed for
approximately 2 seconds to activate the remote start
function and then released within a maximum of 7
seconds or a Remote Start Failure alarm will occur.
WARNING
!
This machine is remote
start and stop equipped.
May start or stop at
anytime.
Can cause severe injury or
death.
Disconnect power before
servicing.
Lock and tag out.
See Operators / Instruction
Manual.