Lincoln 500 Welding System User Manual


 
Vantage 500 CUMMINS
A-7 INSTALLATION A-7
2. Take necessary steps to assure load is limited to the capacity
of the Vantage by installing a 50 amp, 240 VAC double pole
circuit breaker. Maximum rated load for each leg of the 240
VAC auxiliary is 50 amps. Loading above the rated output will
reduce output voltage below the allowable -10% of rated
voltage which may damage appliances or other motor-driven
equipment and may result in overheating of the Vantage
engine.
3. Install a 50 amp 120/240 VAC plug (NEMA Type 14-50) to the
double-pole circuit breaker using No. 6, 4 conductor cable of
the desired length. (The 50 amp, 120/240 VAC plug is
available in the optional K802R plug kit.)
4. Plug this cable into the 50 Amp 120/240 Volt receptacle on the
Vantage case front.
Figure A.2 Connection of the Vantage to Premises Wiring
240 Volt
60 Hz.
3-Wire
Service
POWER
COMPANY
METER
240 VOLT
120 VOLT
120 VOLT
LOAD
N
NEUTRAL
BUS
GROUND
PREMISES
DISCONNECT AND
SERVICE
OVERCURRENT
PROTECTION
GND
N
NOTE: No. 6 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
240 VOLT
GROUNDED CONDUCTOR
50AMP
240 VOLT
DOUBLE
POLE
CIRCUIT
BREAKER
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
50 AMP, 120/240
VOLT PLUG
NEMA TYPE 14-50
50 AMP, 120/240 VOLT
RECEPTACLE